Place Holder Barrier – K-System
Versions
KCD0-LGH
empty housing, internal connection via
jumpers possible, for intrinsically safe
and non-intrinsically safe circuits
KFD0-LGH
empty housing, internal connection via
jumpers possible, for intrinsically safe
and non-intrinsically safe circuits
KFD0-LGH-5T
empty housing, internal connection via
jumpers possible, for intrinsically safe
and non-intrinsically safe circuits,
5 terminals
KFD0-LGH-Y34868 empty housing, no internal connection
possible
KFD0-LGH-Y39343 empty housing, internal connection via
DIP switches possible, for intrinsically
safe and non-intrinsically safe circuits
KFD0-LGH-GN
empty housing, internal connection via
jumpers possible, only for intrinsically
safe circuits
Safety information
The corresponding data sheets and the declaration of
conformity are an integral part of this document.
Intended use
Laws and regulations applicable to the usage or planned
purpose of usage must be observed. Devices are only
approved for proper usage in accordance with intended use.
Improper handling will result in voiding of any warrantee or
manufacturer's responsibility.
The devices are not suitable for the isolation of signals in
power engineering.
Protection of operating personnel and the system is not
ensured if the product is not used in accordance with its
intended use.
Installation and commissioning
Commissioning and installation must be carried out by
specially trained and qualified personnel only.
Installation of the interface devices in the
safe area
The devices are constructed to satisfy the IP20 protection
classification and must be protected from adverse
environmental conditions such as water spray or dirt
exceeding the pollution degree 2.
The devices must be installed outside the hazardous area!
The installation of the intrinsically safe circuits is to be
conducted in accordance with the relevant installation
regulations. It is especially important to ensure that all non-
intrinsically safe circuits are safely isolated (see section
"Internal connections").
Subject to modifications without notice
Pepperl+Fuchs Group
USA: +1 330 486 0002
www.pepperl-fuchs.com
pa-info@us.pepperl-fuchs.com
The respective peak values of the field device and the
associated device with regard to explosion protection should
be considered when connecting intrinsically safe field devices
with the intrinsically safe circuits of devices (demonstration of
intrinsic safety). EN 60079-14/IEC 60079-14 is to be observed
(where appropriate). The K*D0-LGH* is passive, the
intrinsically safe data corresponds to that in the connected
devices.
When connecting several intrinsically safe current circuits,
these current circuits are to be considered as connected.
Installation and commissioning of the
interface devices within Zone 2/Div. 2 of the
hazardous area
Only devices with the corresponding manufacturer's
declaration of conformity or separate certificate of conformity
can be installed in Zone 2/Div. 2.
The individual data sheets indicate whether these conditions
are met.
The devices should be installed in a switch or junction box that:
meets at least IP54 in accordance to EN 60529.
meets to the requirements of resistance to light and
resistance to impact according to EN 60079-0/
IEC 60079-0.
meets to the requirements of thermal endurance according
to EN 60079-15/IEC 60079-15.
must not cause ignition danger by electrostatic charge
during intended use, maintenance and cleaning.
The installation of the intrinsically safe circuits is to be
conducted in accordance with the relevant installation
regulations. It is especially important to ensure that all non-
intrinsically safe circuits are safely isolated (see section
"Internal connections").
The respective peak values of the field device and the
associated device with regard to explosion protection should
be considered when connecting intrinsically safe field devices
with the intrinsically safe circuits of devices (demonstration of
intrinsic safety). EN 60079-14/IEC 60079-14 is to be observed
(where appropriate). The K*D0-LGH* is passive, the
intrinsically safe data corresponds to that in the connected
devices.
When connecting several intrinsically safe current circuits,
these current circuits are to be considered as connected.
The manufacturer's declaration of conformity should be
observed. It is especially important to observe the "special
conditions" if these are included in the certificates.
Repair and maintenance
Maintenance is not required.
Fault elimination
Only those changes that are listed in the section "Internal
connections" may be performed on devices that are operated
in connection with hazardous areas. Repairs to a device may
also only be performed at these locations.
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Singapore: +65 6779 9091
pa-info@de.pepperl-fuchs.com
pa-info@sg.pepperl-fuchs.com
Operating Instructions
1

Advertisement

loading

Summary of Contents for Pepperl+Fuchs KCDO-LGH

  • Page 1 Repairs to a device may also only be performed at these locations. Subject to modifications without notice Copyright Pepperl+Fuchs Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 www.pepperl-fuchs.com...
  • Page 2 1 x 2.5 mm (14 AWG) Subject to modifications without notice Copyright Pepperl+Fuchs Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 www.pepperl-fuchs.com...

This manual is also suitable for:

Kfdo-lghKfd0-lgh-5tKfd0-lgh-y34868Kfd0-lgh-y39343Kfdo-lgh-gn