Technical data (Transfer Application)
1.
Mechanism side
2.
Mechanism opposite side
3.
End cap with mesh
L1 End cap length mechanism side
Minimum distances
1.
Side vertical wall
2.
Floor
a.
Distance between fire dampers installed within vertical wall
Installation
EI 120 S Installation within vertical rigid wall
EI 120 S Installation within vertical light wall (plasterboard)
EI 120 S Installation within vertical light wall (plasterboard)
EI 120 S Installation within vertical light wall (gypsum blocks wall)
EI 90 S Installation within vertical light wall (gypsum blocks wall)
EI 120 S Installation within floor
EI 90 S Installation within floor
L2 End cap length mechanism
opposite side
Ø
Fire damper nominal diameter
Length of end cap with mesh depending on fire damper di-
ameter Ø.
Ø
100
125
140
150
160
180
200
224
250
280
300
315
Ø
Fire damper nominal diameter
L1
End cap length mechanism side
L2
End cap length mechanism opposite side
Minimum distances
It is recommended to keep enough space for using the control
mechanism or for maintenance.
In accordance with Articles 7 and 13 of EN 1366-2 respect the mini-
mum distances indicated below.
b.
Distance between fire damper and vertical lateral wall / floor
c.
Distance between fire dampers installed within floor
d.
Distance between fire damper and vertical lateral wall
Fire dampers installed within vertical wall
a [mm]
b [mm]
200
75
200
75
200
75
200
75
200
75
-
-
-
-
L1
L2
40
40
40
40
40
40
40
40
40
40
40
40
40
60
40
40
60
80
60
100
60
100
60
120
Fire dampers installed within floor
c [mm]
d [mm]
-
-
-
-
-
-
-
-
-
-
200
75
200
75
9/16