Kaco blueplanet hy-switch Operating Instructions Manual page 23

Accessories for hybrid inverters
Table of Contents

Advertisement

The integration of the component into the local installation must be chosen
correctly. Typically, it is installed after the utility company's counter and before the
first load output. Observed the integration options shown in 8.2 .
↻ Component is securely mounted (see7.2).
1.
Determine the connection point for integrating the component into
the local installation.
2.
Switch off all inverters, all local generators and the grid connection.
3.
Establish the connection points for the component in the control cabinet.
4.
Note the required cable cross-sections:
5.
Insert the cable into the component and into the control cabinet.
6.
Insulate all wires of the cable properly.
Wire the component on the cable clamps with
7.
1.
2.
hy-switch for KACO blueplanet hybrid inverters
WARNING
To avoid the risk of fire or electric shock, make sure that
the wiring is in good condition and not undersized. Never install
defective or inferior cables. Cable connections may only be be
connected or disconnected without power.
NOTE
Fuse protection of max. 50 A required
A fuse protection of max. 50 A is required in the connection line
of the component.
Insert the cables through the cable gland.
Connect PE
Higher currents can damage the component.
[
S_2.5] (see Fig. 9):