6.6 Safety Monitoring

When Safety Monitoring is enabled the 09827 control board communicates with the safety sensor before every dangerous
movement of the door to ensure that the Safety inputs are functioning correctly and all wires are in place. That is, before
the door is opened and before the door is closed there is communication between the 09827 and safety sensor.
SETUP
1
Wire safety sensor to board as per wiring diagram below. Or according to the wiring diagrams for individual
sensors in the pages to follow.
2
If not already done, enable for safety monitoring. For BEA sensors this must be done with the remote control.
3
Check to see that door opens.
4
In order to ensure that the safety monitoring setup has been done properly unplug the SM1 and/or
SM2A connectors separately to see that the door does not open when triggered. (Overload LED will flash 1/3sec).
Plug these connectors back into the board once this test is complete.
CONNECTION TO SAFETY SENSOR
FOR SAFETY MONITORING
OF BOTH H.A. AND F.A. BOARDS
BOARD #09827-HA & 09827-FA
SM2A (Safety monitor 2) is
enable in setting "A" "A".
SENSOR # 2
SAFETY SIGNAL
SAFETY COM
SAFETY MON -
SAFETY MON +
SM1 (Safety monitor 1) is
enable in setting "A" "9"
SENSOR # 1
SAFETY SIGNAL
SAFETY COM
SAFETY MON -
SAFETY MON +
6.0 DIGITAL BOARD & PROGRAMMING
A failed communication before opening will prevent the door from opening.
A failed communication before closing will prevent the door from closing.
For any failed communication the Overload LED will flash.
BLACK
SAFETY MONITOR -
RED
SAFETY MONITOR +
BLACK
SAFETY MONITOR -
RED
SAFETY MONITOR +
Record Canada Inc.
Toll Free: 1-877-348-6837
info.ditec.ca@recorddoors.com
www.recorddoors.ca
Record USA Inc.
Toll Free: 1-866-901-4284
info.ditec.us@recorddoors.com
www.recorddoors.com
Pg. 53
HA8-SP Manual V. 7.0