Siemens Symaro QAA2890/WI Manual page 5

Wireless room sensor
Hide thumbs Also See for Symaro QAA2890/WI:
Table of Contents

Advertisement

Radio frequency energy
Interference to radio communications
Install and use equipment in accordance with installation guide.
Read all regulatory compliance information.
Mounting
Location
The device is designed for wall mounting, flush mounting and tape mounting.
Install in indoor environments (device is not suitable for outdoor use); do not install in
recesses, behind curtains, above or close to heat sources or shelves and not on walls
where a chimney is located. Do not expose the unit to spot lights or direct sunlight.
Do not install the device in a cabinet or metal container.
Install the sensor in the occupied space about 1.5 m above the floor, at least 20 cm from
the next wall.
Seal the end of the conduit at the sensor to prevent false measurements caused by
draughts through the conduit.
Mounting instructions are enclosed in the package.
Mounting
instructions
The humidity sensor is a sensitive measuring device and must be handled with care.
Chemical vapors
Chemical vapors at high concentration in combination with long exposure times may distort
the sensor reading.
Avoid direct contact with chemicals in any form. Do not touch sensitive components with
bare hands or tools as this will negatively impact measurement accuracy.
Siemens
Smart Infrastructure
NOTICE
NOTICE
5
A6V12871702_en--_a
2023-03-14