ICM Controls ICM325A Installation, Operation & Application Manual

ICM Controls ICM325A Installation, Operation & Application Manual

Single phase universal head pressure control

Advertisement

Quick Links

INSTALLATION, OPERATION & APPLICATION GUIDE
For more information on our complete range of American-made products – plus wiring diagrams,
troubleshooting tips and more, visit us at www.icmcontrols.com
FEATURES
• Near field communication using the ICM OMNI App
• Inputs for two temperature sensors or two pressure sensors
• Heat pump bypass for full speed operation in heating mode
• Jumper selectable control voltage enabling
• Universal input voltage 120-600 VAC
• Universal Control voltage 24-240 VAC (jumper enabled)
CAUTION!
Installation of the ICM325A shall be performed by trained technicians only. Adhere
to all local and national electric codes.
Disconnect all power to the system before making any connections.
SPECIFICATIONS
• Line voltage: 120 - 600 VAC
• Control voltage: 24-240 VAC (Jumper enabled)
• Motor 2 Output: 10A maximum
• Frequency: 50-60 Hz
• Operating temperature: -40ºF to +167ºF (-40°C to +75°C)
• Temperature sensor: ICM386
• Pressure sensor: ICM387
• Heat pump reversing valve input: 24-240 VAC (Heat active default / jumper
enabled cool active option)
• Mounting:
– Surface mount using (4) #8 screws
– The ICM325A should be surface mounted to a clean metal or other thermally
conductive surface for maximum heat dissipation
• Motor:
– The ICM325A is intended to be used with single phase permanent split
capacitor motors which are capable of having the input voltage varied.
MOUNTING THE PROBE
1. Install the temperature probe several bends into the condenser. It can
be attached to the U-bend or placed between the fins in the upper 1/3
of the condenser (see other side for more information).
Note: The response of the system can be fine tuned by repositioning
the probe to a location which satisfies the desired pressure or by
adjusting the set point.
2. Connect the two wires from the sensor to the terminal block where it is marked
T1/P1. If additional probes are necessary for multiple refrigerant circuits, they
may be attached to terminals marked T2/P2.
Note: The control will respond to the probe that senses the highest temperature or pressure.
CONTROL VOLTAGE SETTING
The optional Control Voltage Enable Jumper activates a universal control voltage input
which allows a control voltage to determine when the ICM325A becomes active. The
control voltage is defaulted off from the factory and is not required for operation.
HEAT PUMP OPERATION
During heating mode on a heat pump, varying the fan speed is not desirable so the
ICM325A has a bypass mode which adjusts the outdoor fan to full speed during
heating mode. This is accomplished by reading the voltage of the reversing valve at
the HP RV terminals to indicate whether the unit is in heat mode or cool mode. The
ICM325A is factory set for air conditioning / heat active reversing valves. A jumper
setting (HP O RV) is provided to accommodate cool active reversing valves.
MODE OF OPERATION
The ICM325A is designed to control the head pressure on a heat pump or HVAC unit by
controlling the condenser fan speed thus allowing the heat pump or air conditioner to
operate even when the temperature outdoors is too low for normal operation.
Temperature vs. Output Voltage %
• Full Speed: Temperature sensed
above 100°F [Green LED on]
• Variable Speed: Temperature sensed
between 100°F and 70°F [Orange
LED on]
• Off: Temperature sensed below 70°F
Note: Stated temperatures are based on
default settings.
ICM OMNI APP ADJUSTABLE SETTINGS
PROBE TYPE
Probe Type allows the user to select a Direct Pressure Input or a Indirect
Temperature Input for monitoring head pressure.
SET POINT
Allows the end user to adjust the set point temperature or pressure the user wishes
to maintain.
HARD START SETTING
Adjusts the condenser fan to full speed during startup, allowing lubrication of a
sleeve bearing motor during startup.
MINIMUM OUTPUT VOLTAGE SETTING
Adjusts the range which the control operates in variable speed. The MAX setting
of 48% allows the least amount of variable speed over the range whereas the MIN
setting of 17% allows for the most amount of variable speed over the range.
NOTE: ALL adjustments are made using the ICM Controls OMNI App.
Example
SENSOR REPLACEMENTS
• Temperature Sensor: ICM386
MULTIPLE CONDENSORS UP TO 10 AMPS
Line 1
Line Voltage
Line 2
Terminal to
be used for
480 VAC
Control
Transformer
T-Stat
ICM325A
Single Phase Universal Head Pressure Control
Pressure vs. Output Voltage %
• Full Speed: Pressure sensed above
350 PSI [Green LED on]
• Variable Speed: Pressure sensed
between 310 PSI and 350 PSI [Orange
LED on]
• Off: Pressure sensed below 310 PSI
• Pressure Sensor: ICM387
Motor
The ICM325A can
1
monitor up to
2 condensors
Motor
2
Reversing Valve
for Heat Pump
Condenser

Advertisement

loading

Summary of Contents for ICM Controls ICM325A

  • Page 1 MODE OF OPERATION CAUTION! The ICM325A is designed to control the head pressure on a heat pump or HVAC unit by Installation of the ICM325A shall be performed by trained technicians only. Adhere controlling the condenser fan speed thus allowing the heat pump or air conditioner to to all local and national electric codes.
  • Page 2 (optional) 10° 50° 19.9 Wiring of the ICM325A to a heat pump is the same as for air conditioning with the 15° 59° 15.7 exception of the Motor 2 output and the reversing valve input. For a heat pump, the 20°...
  • Page 3 USING THE NFC TECHNOLOGY NEW UNIVERSAL CONTROLS VIA NFC TECHNOLOGY STEP 1 - Download the app Locate and download the "ICM Omni" app from the Google Play Store or Apple Store. Available on the Available on STEP 2 - STEP 3 - STEP 4 - Open the app Select a...