ICP DAS USA USB-87P1 User Manual page 59

Hide thumbs Also See for USB-87P1:
Table of Contents

Advertisement

(Error)
Configuration
failed
Bright
Cannot find
06H
(Error)
module
Bright
Incorrect
07H
(Error)
module name
Bright
Internal INIT*
08H
(Error)
pin failed
Module
Bright
09H
address over
(Error)
255 (FFh)
The command
count saved to
Bright
0AH
87Pn is not the
(Error)
same as DCON
Utility
The configured commands are wrong for
DCON Protocol.
The configured module at this slot has been
removed. It is empty now.
Configure failure:
The module inserted in this slot is not the
same as previous configured.
Configure failure:
The INIT Pin is failed to connect with the
GND and module failed to initialize.
The module address is over 255 (FFh).
This error might be caused by following
reasons.
1. Command length error.
2. Command checksum error.
3. Communication error during the process
of writing commands to 87Pn.
USB-87P1/2/4/8 User Manual, version: 1.4
2. Click the "Write To 87Pn" button to write the settings to
87Pn CPU again.
1. Please insert a correct module as previous configured
one.
2. Or configure with DCON Utility as "Empty" and click the
"Write To 87Pn" button to write the configuration to
87Pn CPU.
The insert & configure module name are different, insert
the correct one or run the Dcon Utility to modify the
settings accord with the module name.
1. Please restart the power to initialize to I/O module
2. If it still failed to initialize, send it back to factory to
check.
Note: USB-87Pn only supports high profile 87K I/O
modules.
The maximum address of
87P1 is 254 (FEh)
87P2 is 253 (FDh)
87P4 is 251 (FBh)
87P8 is 247 (F7h)
Please configure this 87K I/O module with DCON Utility,
and click the "Write To 87Pn" button to write the
configuration to 87Pn CPU again.
59

Advertisement

Table of Contents
loading

This manual is also suitable for:

Usb-87p2Usb-87p4Usb-87p8

Table of Contents