Siemens SIMATIC NET RUGGEDCOM RS416P Installation Manual page 52

Rugged ethernet switches
Table of Contents

Advertisement

61000-4-3
61000-4-4
61000-4-5
61000-4-6
61000-4-8
61000-4-29
61000-4-11
61000-4-12
61000-4-16
61000-4-17
EC 60225-27
RUGGEDCOM RS416P
Installation Manual, 11/2022, C79000-G8976-1019-11
Test
IEC
Radiated RFI
IEC
Burst (Fast Transient)
IEC
Surge
IEC
Induced (Conducted) RFI
IEC
Magnetic Field
IEC
Voltage Dips and Interrupts
IEC
IEC
Damped Oscillatory
IEC
Mains Frequency Voltage
IEC
Ripple on DC Power Supply
Dielectric Strength
6.2 EMC and Environmental Type Tests
Description
Enclosure Air
Enclosure
ports
Signal ports
DC Power
ports
AC Power
ports
Earth
ground ports
Signal ports
DC Power
ports
AC Power
ports
Signal ports
DC Power
ports
AC Power
ports
Earth
ground ports
Enclosure
ports
DC Power
ports
AC Power
ports
Signal ports
DC Power
ports
AC Power
ports
Signal ports
DC Power
ports
DC Power
ports
Signal ports
DC Power
ports
AC Power
ports
Test Levels
± 15 kV
20 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
2 kV
± 2 kV line-to-earth,
± 1 kV line-to-line
± 4 kV line-to-earth,
± 2 kV line-to-line
10 V
10 V
10 V
10 V
100 A/m
1000 A/m for 3 s
30% for 0.1 s,
100% for 0.05 s
30% for 1 period,
100% for 5 periods,
100% for 250 periods
2.5 kV common, 1 kV
differential mode @ 1 MHz
2.5 kV common, 1 kV
differential mode @ 1 MHz
2.5 kV common, 1 kV
differential mode @ 1 MHz
30 V Continuous,
300 V for 1 s
30 V Continuous,
300 V for 1 s
± 15%
2 kVAC  (Fail-
Safe Relay output)
1.5 kV
2 kV
Certification
Severity
Levels
4
a
Note
a
Note
4
4
4
3
3
4
3
3
3
3
a
Note
5
 
 
3
3
3
4
4
4
 
 
 
43

Advertisement