Atlantic alfea hybrid duo 11 Installation And Commissioning Instructions

Atlantic alfea hybrid duo 11 Installation And Commissioning Instructions

Water/air heat pump with integrated fuel oil burner, single phase or three phase split, 2 services
Hide thumbs Also See for alfea hybrid duo 11:
Table of Contents

Advertisement

alféa hybrid duo oil low NOx
Water/air heat pump
with integrated fuel oil burner,
single phase or three phase
split, 2 services
Outdoor unit
WOYG112LCT
WOYG140LCT
WOYK112LCT
WOYK140LCT
WOYK160LCT
Hydraulic module
024208
Document n° 1605-3 ~ 17/09/2013
FR
EN
ES
PT
ES
ES
ES
ES
Installation and
commissioning
instructions
for professionals
To be kept by the user
for future reference
atlantic-comfort.com
The specifications of this equipment may
be modified without prior instructions
Non-contractual document.
IT

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the alfea hybrid duo 11 and is the answer not in the manual?

Questions and answers

Summary of Contents for Atlantic alfea hybrid duo 11

  • Page 1 2 services Outdoor unit Hydraulic module WOYG112LCT 024208 WOYG140LCT WOYK112LCT WOYK140LCT WOYK160LCT Installation and commissioning instructions for professionals To be kept by the user for future reference atlantic-comfort.com The specifications of this equipment may be modified without prior instructions Non-contractual document.
  • Page 2: Table Of Contents

    alfea hybrid duo heat pump oil low NOx CH Contents Presentation of the equipment . . . . . . . . . . . . . . . . . . . . . . . . . 4 Packaging General characteristics Description...
  • Page 3 alfea hybrid duo heat pump oil low NOx CH " The following are required for the installation of this appliance: - work must only be carried out by qualified personnel with a certificate of aptitude for handling refrigerating fluids (in compliance with article R543.106 of the Environmental code), - a heating technician must be involved .
  • Page 4: Presentation Of The Equipment

    alfea hybrid duo heat pump oil low NOx CH 1 Presentation of the equipment 1 .1 Packaging • 1 box: Outdoor unit. • 1 box: Hydraulic module with NOx low burner and outdoor temperature probe. Pairing table Heat pump Outdoor unit Hybrid duo hydraulic module Model ref.
  • Page 5 alfea hybrid duo heat pump oil low NOx CH Denomination : alféa hybrid duo oil low NOx flue model 14 + 11 3 ph . 14 3 ph . 16 3 ph . Electrical characteristics Voltage (50 HZ) Maximum current of the appliance 10 5 Nominal current 11 4...
  • Page 6 alfea hybrid duo heat pump oil low NOx CH " outdoor unit, model hybrid duo oil low NOx 11 model hybrid duo oil low NOx 14 + Drain hole (Ø 20) 4 holes (Ø 10) Orifice d’écoulement (Ø 20) 4 trous Ø 10 Bottom view Vu e de dessous 1290...
  • Page 7 alfea hybrid duo heat pump oil low NOx CH " Hydraulic module Flexible hoses 1075 Ø 20x27 female Ø 26x34 male Ø int. ext. smoke outlet 125 / 139 1711 1682 Liquid 3/8” Gas 5/8” Fuel hose passages Rear view Side view Front view figure 2 - Dimensions in mm...
  • Page 8 alfea hybrid duo heat pump oil low NOx CH outdoor probe QAC34 Ω 43907 1 kΩ, 25 °C 10000 2490 1000 °C Heat pump return sensor Heat pump start sensor Ω 32500 30000 figure 7 - Head losses of the combustion circuit 27500 25000 22500...
  • Page 9: Description

    alfea hybrid duo heat pump oil low NOx CH 1 .6 Description " Model " Model hybrid duo oil low NOx 11 and 14 + single phase hybrid duo oil low NOx 11, 14 and 16 3 phase WO*K1**LCT Legend: High performance impeller and low noise level.
  • Page 10 alfea hybrid duo heat pump oil low NOx CH Legend Condenser 23 Heater start sensor 12 Heating circulation pump Liquid refrigeration connection 24 Domestic sensor 13 Domestic circulation pump Gas refrigeration connection Control panel 14 Drain valve Combustion chamber 15 Safety valve 25 User interface Reversible chamber door 16 Manual drain tap...
  • Page 11: Operating Principle

    alfea hybrid duo heat pump oil low NOx CH 1 .7 Operating principle Priority is given to the operation of the heat pump. When the heat pump is not sufficient for the heating, the The heat pump transmits the energy in the outdoor air burner automatically takes over.
  • Page 12 alfea hybrid duo heat pump oil low NOx CH • Operating principle of the domestic hot water Increase in temperature of the tank (without drawing) (DHW) sanitary water temperatures (SHW) °C programmed: comfort temperature (line 1610 at 65 °C) and reduced temperature (line 1612 àat40 °C).
  • Page 13: Installation

    alfea hybrid duo heat pump oil low NOx CH 2 Installation 2 .1 Statutory conditions 2 .3 Unpacking and reserves for installation and servicing 2 .3 .1 Receipt The appliance must be installed and the maintained by an approved professional in accordance with the When the courier is present, carefully check the general prevailing regulations and code of practice, in particular: appearance of the appliances, check that the outdoor...
  • Page 14: Containment Of Refrigerant Circuits

    alfea hybrid duo heat pump oil low NOx CH 2 .4 Positioning 2 .3 .4 Containment of refrigerant circuits All refrigerant circuits fear contamination from dust and The choice of the position is particularly important moisture. If such pollutants introduced into refrigeration as having to move it later is a delicate operation that circuit, they can contribute to degrade the reliability of requires a qualified person.
  • Page 15 alfea hybrid duo heat pump oil low NOx CH 1000 or more 1000 or more 1500 1000 Max. 500 Max. 500 or more or more or more 1500 1500 or more or more 1500 or more 1500 2000 3000 or more or more or more 1500...
  • Page 16: Fitting The Outdoor Unit

    alfea hybrid duo heat pump oil low NOx CH 2 .5 .2 Fitting the outdoor unit The outdoor unit must be raised by at least 50 mm from the ground. In snowy regions, this height must be increased but must not exceed 1.5 m. - Attach the outdoor unit using screw and spring or split washers to ensure they do not come loose.
  • Page 17: Reversible Chamber Door

    alfea hybrid duo heat pump oil low NOx CH with a free cross section that cannot be obstructed of at least 50 cm that opens onto the lower part and a used  air outlet (B) with a free cross section that cannot be obstructed of at least 100 cm positioned on the upper part and opening directly outdoors (see...
  • Page 18: Connection Pipe

    alfea hybrid duo heat pump oil low NOx CH 2 .6 .4 Connection pipe 40 cm The evacuation pipe must comply with the regulations 1,2 m in force < 15° The cross section of the connection pipe must not be smaller than the outlet nozzle of the appliance.
  • Page 19: Flaring

    alfea hybrid duo heat pump oil low NOx CH 2 .7 .2 Refrigerating connections The connection between the outdoor unit and the Hydraulic module must only be made with new copper connectors (refrigerating quality) and individually insulated. Flare Respect the diameters of the pipes and the authorised Expander lengths(figure 21, page 20).
  • Page 20: Connecting The Flare Connections

    alfea hybrid duo heat pump oil low NOx CH 2 .7 .5 Connecting the flare connections " The connections must be made the day the gas - Remove the plugs from the pipes and refrigerating is connected to the installation (see § 2.8, page connections 21).
  • Page 21: Commissioning The Refrigerating Gas Installation

    alfea hybrid duo heat pump oil low NOx CH 2 .8 Commissioning APPENDIX 2 the refrigerating gas installation Method 3 empty " This operation is only to be carried out by qualified fitters in compliance with the legislation - Connect the high pressure flexible of the manifold for the handling of refrigerating fluids.
  • Page 22: Final Leak Test

    alfea hybrid duo heat pump oil low NOx CH • First leak test Refrigerating connector (gas) - Remove the protection plug (B) from the filling orifice Liaison frigorifique (Schrader) on the gas valve (large diameter). Plug (A) Bouchon (A) - Connect the high pressure flexible hose of the Manifold 3 way valve Vanne 3 voies to the filling orifice...
  • Page 23: Additional Volume Added

    alfea hybrid duo heat pump oil low NOx CH in the outdoor unit 50 g of R410A per additional metre " Only for the 3 phase models Length of the Carry out the following procedures to collect the 15 m 20 m max.
  • Page 24: Hydraulic Connection

    alfea hybrid duo heat pump oil low NOx CH 2 .9 Hydraulic connection 2 .9 .1 General The connection must comply with trade practices There is no need for glycol. If water containing glycol according to the regulations in force. is used, carry out an annual check of the quality of the glycol The use of glycol monoethylene is prohibited .
  • Page 25: Connection To The Domestic Circuit

    alfea hybrid duo heat pump oil low NOx CH 2 .9 .2 Connection to the domestic circuit Place a safety group with a valve calibrated to 7 bar Valve closed on the cold water inlet, and connect an evacuation pipe (normal operating position) leading to the drain.
  • Page 26: Connection Of The Fuel Supply

    alfea hybrid duo heat pump oil low NOx CH 2.10 Connection of the fuel supply Refer to the instructions supplied with the burner. In order for the burner to operate correctly, a filter (60 μm) must be installed on the fuel supply pipe. "...
  • Page 27: Overall View Of The Electrical Connections

    alfea hybrid duo heat pump oil low NOx CH 2 .11 .3 Overall view of the electrical connections The electrical wiring diagram of the hydraulic module is detailed on figure 51, page 56 Central ambient radio unit T78 (option) Centrale ambiance radio T78 (option) Outdoor probe Sonde extérieure...
  • Page 28: Electrical Connections On The Outdoor Unit Side For Single Phase Model

    alfea hybrid duo heat pump oil low NOx CH 2 .11 .5 Electrical connections on the outdoor unit side for single phase model Access to the connector terminals - Remove the front panel. Remove the screws and the - Make the connections as per diagram (figure 34 and cover of the front panel.
  • Page 29: Electrical Connections On The Outdoor Unit Side For 3 Phase Model

    alfea hybrid duo heat pump oil low NOx CH 2 .11 .6 Electrical connections on the - Use the cable clamps to avoid any accidental outdoor unit side for 3 phase model disconnection of the conductive wires. - Obstruct the space at the cable inlet in the outdoor unit Access to the connector terminals with the insulating plate.
  • Page 30: Electrical Connections On Hydraulic Module Side

    alfea hybrid duo heat pump oil low NOx CH 2 .11 .7 Electrical connections on Hydraulic module side Grommets (power) Terminal blocks Stuffing gland (probes) Heat pump regulator Interface board figure 39 - Access to hydraulic unit electric box and description Access to the connector terminals •...
  • Page 31 alfea hybrid duo heat pump oil low NOx CH " Single phase model Interconnection between outdoor unit Electrical and hydraulic module power supply Burner 230 V green/yellow blue brown single phase outdoor unit Hydraulic module " Three phase model three phase outdoor unit Burner green/yellow 1 2 3 L1 L2 L3 N...
  • Page 32 alfea hybrid duo heat pump oil low NOx CH HP/HC meter Load shedding or EJP Contact d'information Délestage ou EJP information contact* (deletion of peak day) du compteur HP/HC * (Effacement Jour de Pointe) If the controlling part does not provide * Si l'organe de commande ne délivre a contact that has free potential, the pas de contact libre de potentiel il...
  • Page 33: Outdoor Sensor

    alfea hybrid duo heat pump oil low NOx CH 2 .12 Outdoor sensor 2 .13 Ambient sensor and/or central ambient unit (radio) The Outdoor sensor is required for the correct operation of the heat pump The ambient sensor (or the central ambient unit) is optional Consult the assembly instructions on the packaging of the sensor.
  • Page 34: Verifications And Commissioning

    alfea hybrid duo heat pump oil low NOx CH 2 .14 Verifications and commissioning • Carry out the usual verifications on the burner and its power supply circuit. • Check the turbulators are fitted correctly. Start/Stop • Check correct assembly of electrical connections on the terminals.Check draught.
  • Page 35: Configuration Of The Ambient Probe

    alfea hybrid duo heat pump oil low NOx CH 2 .16 Configuration 2 .17 Configuration of the Ambient probe of the central ambient unit (radio) T55 or T58 To set the ambient probe and link it to T75 - During commissioning, after initialising for around the correct heating zone: 3 minutes, the user language must be set: - Press for more than 3s the presence button...
  • Page 36: Regulation

    alfea hybrid duo heat pump oil low NOx CH 3 Regulation 3 .1 The user interface, the ambient sensor (option) and the central ambient unit (option) User interface Auto Auto °C central ambient unit T75 / T78 ambient probe T55 / T58 figure 43 - - 36 - Installation and operating manual "1605 - EN"...
  • Page 37 alfea hybrid duo heat pump oil low NOx CH item Functions - Definitions of the functions Selecting the DHW operating mode - Operation: Production of DHW in function of the timer programme. - Stopping: Production of the DHW stopped with antifreeze function of the domestic water active.
  • Page 38 alfea hybrid duo heat pump oil low NOx CH 3 .2 Description of the display 3 .3 Water logic The operation of the heat pump is controlled by the water logic. The reference temperature of the heating circuit water is adjusted in function of the outdoor temperature. If there are thermostatic valves fitted to the installation, they must be opened fully or set higher than the normal value of the ambient temperature.
  • Page 39 alfea hybrid duo heat pump oil low NOx CH water law slopes 2,75 ° C radiator 2,25 High and medium temperature 1,75 Burner operation 1,25 radiator Heat pump/burner operation low temperature 0,75 Floor heating Heat pump operation alone system 0,25 °...
  • Page 40: Regulation Parameters

    alfea hybrid duo heat pump oil low NOx CH 3 .4 Regulation parameters 3 .4 .2 Setting the parameters 3 .4 .1 General - Selecting the desired level. Only the parameters accessible at the levels: - Scroll the list of menus. U - Final user.
  • Page 41 alfea hybrid duo heat pump oil low NOx CH Line Function Setting range or display Setting increment Basic setting Operation HC2 (command HC2) Common to CC1, independent Common with heating circuit 1 Common to CC1 or independent This function permits the choice to be made if the ambient sensor (in option) has an action on the two zones or on a single zone.
  • Page 42 alfea hybrid duo heat pump oil low NOx CH Line Function Setting range or display Setting increment Basic setting Time program 5 / Cooling (Not available with DHW model). Holidays, circuit 1 Period 1 Pre-selection of the holiday period Period 1 to 8 Date of start of holidays (day/month).
  • Page 43 alfea hybrid duo heat pump oil low NOx CH Line Function Setting range or display Setting increment Basic setting Max. optimisation when switching off 360 min 10 min 120 min (anticipation of stoppage to switch from comfort to reduced) Start increasing the reduced operation -30...
  • Page 44 alfea hybrid duo heat pump oil low NOx CH Line Function Setting range or display Setting increment Basic setting Setting the heating, circuit 2 If the installation is composed of 2 heating circuits (only displayed with 2nd circuit kit option) 20 °C 1010 Ambient comfort temperature value...
  • Page 45 alfea hybrid duo heat pump oil low NOx CH Line Function Setting range or display Setting increment Basic setting 1200 Operating mode changeover None, protection mode, Protection reduced, comfort, Automatic mode Operating mode at the end of floor drying. Setting the DHW (domestic hot water) 1610 DHW nominal set point reduced reference value (defined...
  • Page 46 alfea hybrid duo heat pump oil low NOx CH Line Function Setting range or display Setting increment Basic setting 2910 Liberation dependent on outdoor T° -30... 30 °C 1 °C 2920 In case of EJP blocking signal (EX4) Locked (locked waiting)... Blocked while Liberated waiting...
  • Page 47 alfea hybrid duo heat pump oil low NOx CH Line Function Setting range or display Setting increment Basic setting Error 6711 Reset HP No, Yes 6740 Initial alarm T° heating circuit1 --, 10... --, 10... 240 min 10 min 6741 Initial alarm T°...
  • Page 48 alfea hybrid duo heat pump oil low NOx CH Line Function Setting range or display Setting increment Basic setting Test of inputs/outputs 7700 Relay test No test This test consists of commanding the regulator relays one by one and checking the outputs. This permits a check that the relays are operating and that the wiring is correct (for this, check that each appliance is operating on the installation).
  • Page 49 alfea hybrid duo heat pump oil low NOx CH Line Function Setting range or display Setting increment Basic setting 8056 History 4 Date, time, state code 8058 History 5 Date, time, state code 8060 History 6 Date, time, state code 8062 History 7 Date, time, state code...
  • Page 50 alfea hybrid duo heat pump oil low NOx CH Line Function Setting range or display Setting increment Basic setting Start temperature ref. value 1 50 °C 8756 Cooling start temperature 1 0... 140 °C Initial cooling temperature reference value 8760 Pump CC2 Stop, Start Stop...
  • Page 51 alfea hybrid duo heat pump oil low NOx CH  Installation and operating manual "1605 - EN" - 51 -...
  • Page 52: Overall View Of The Electrical Connections

    alfea hybrid duo heat pump oil low NOx CH 4 Overall view of the electrical connections • Configuration 13: 1 heating circuit. - 52 - Installation and operating manual "1605 - EN"...
  • Page 53 alfea hybrid duo heat pump oil low NOx CH • Configuration 14: 2 heating circuits. Installation and operating manual "1605 - EN" - 53 -...
  • Page 54: Electrical Wiring Diagrams

    alfea hybrid duo heat pump oil low NOx CH 5 Electrical wiring diagrams Pressure Option (connector) Inverter board switch see the technical instructions Temp. sensor. Compressor Temp. sensor. Outdoor Temp. sensor. Evaporator Temp. sensor. Back-flow Pressure Fuse regulator coil Temp. sensor. radiator F4 T 5A - 250 V Temp.
  • Page 55 alfea hybrid duo heat pump oil low NOx CH Re-injection pressure regulator coil Re-injection coil Temp. sensor. Pressure Inverter board regulator. Temp. sensor. Evaporator medium Temp. sensor. radiator P.F.C. Temp. sensor. Back-flow Temp. sensor. Evaporator outlet Compressor Temp. sensor. Temp. sensor. Outdoor Condenser Inverter...
  • Page 56 alfea hybrid duo heat pump oil low NOx CH Domestic circulation pump Burner Heating circulation pump Mixing valve Colour codes connections on terminals BK Black (see figure 39, page BN brown BU Blue ON/OFF switch burner ON LED burner safey LED Safety thermostat Timed relay connections on the PAC regulator, accessories and...
  • Page 57: Breakdown Diagnosis And Information

    alfea hybrid duo heat pump oil low NOx CH 6 Breakdown diagnosis and information Depending on whether the fault is from the outdoor unit the display shows the symbol or the Hydraulic module, the fault may be signalled by the digital display or the diode on the interface boards. Press the button to obtain details on the origin of 6 .1...
  • Page 58: Faults Displayed On The Single Phase Outdoor Unit

    alfea hybrid duo heat pump oil low NOx CH 6 .2 Faults displayed on the single phase outdoor unit To access the electronic board, the front panel (RH side) must be removed from the outdoor unit. The faults are coded by the flashes of the LED. When an error occurs: The diode "ERROR"...
  • Page 59: Faults Displayed On The 3 Phase Outdoor Unit

    alfea hybrid duo heat pump oil low NOx CH 6 .3 Faults displayed on the 3 phase outdoor unit Diodes and switches To access the electronic board, the front panel (RH side) must be removed from the outdoor unit. The faults are coded by the flashes of the LED. When an error occurs: The diode "ERROR"...
  • Page 60: Display Information

    alfea hybrid duo heat pump oil low NOx CH 6 .4 Display information Designation Line Current drying value. The Info button calls up various information. Current drying day Depending on the appliance type, the configuration and Drying days completed. the state of operation, certain information lines may not State of heat pump 8006 be available.
  • Page 61 alfea hybrid duo heat pump oil low NOx CH  Installation and operating manual "1605 - EN" - 61 -...
  • Page 62: Servicing Of The Installation

    alfea hybrid duo heat pump oil low NOx CH 7 Servicing of the installation 7 .4 Checking the electrical circuit Before carrying out any work, ensure that the general electrical power supply and the fuel supply valve are - Check connections and possible tightening. switched off.
  • Page 63 alfea hybrid duo heat pump oil low NOx CH figure 55 - Access to the flue exchanger "sweeping" button figure 56 - Sweeping function Installation and operating manual "1605 - EN" - 63 -...
  • Page 64: Start-Up Procedure

    alfea hybrid duo heat pump oil low NOx CH 8 Start-up procedure Before switching on the hydraulic unit: • Ensure that all of the DIP SW on the interface board are in the OFF position before starting. • Check the electrical wiring. •...
  • Page 65: Starting-Up

    alfea hybrid duo heat pump oil low NOx CH 8 .1 .2 Starting-up • Switching On (see "Commissioning" chapter § 2.14, page 34 Non conforming and § Page40). Engage the main circuit breaker of the installation (outdoor unit power supply) 2 hours before carrying out the tests =>...
  • Page 66: Start-Up Check-List 64 Settings Sheet

    alfea hybrid duo heat pump oil low NOx CH 8 .2 Settings sheet Parameter Designation Menus Parameter Designation Menus Preliminary settings Boiler measurement (if boiler measure. kit) language inter. user 3700 Outdoor T° to author. operation addit. gener. hours / minutes 3705 time stopped time and...
  • Page 67 alfea hybrid duo heat pump oil low NOx CH 8 .3 Start-up data sheet Site Installer Serial N° Serial N° Outdoor unit Hydraulic module model model Refrigerant type Refrigerant charge Checks Operating voltage & current on outdoor unit Compliance with positioning distances L/N or L1/N Correct evacuation of condensates L2/N...
  • Page 68: Values To Be Given To The User

    Please contact the installer or local authority for more information. * subject to the national law of each member state Date of installation : www. atlantic-comfort.com www.atlantic.fr Société Industrielle de Chauffage SATC - BP 64 - 59660 MERVILLE - FRANCE...

Table of Contents