Refrigerant Safety Standards / Device Connection Limitations - LG LV120HCV Installation Manual

Single zone vertical air handling unit - cv
Table of Contents

Advertisement

Refrigerant Safety Standards
ASHRAE Standards 15-2010 and 34-2010 address refrigerant safety and the maximum allowable
concentration of refrigerant in an occupied space. Refrigerant will dissipate into the atmosphere, but a
certain volume of air is required to safely dissipate the refrigerant. For R410A refrigerant, the maximum
allowable concentration of refrigerant is 26 lbs./1,000 cubic feet (Addendum L modified the RCL to 26) of
occupied spaces. Buildings with 24-hour occupancy are allowed half of that concentration.
If the system develops a refrigerant leak, the entire refrigerant charge of the system will dump into the
area where the leak occurs. To meet ASHRAE Standards 15 and 34, the smallest room volume on the
system must be calculated and compared to the maximum allowable concentration. Also consult state
and local codes in regards to refrigerant safety.
Connection Limitations
Single zone systems consist of one outdoor unit and one indoor unit. One of the most critical elements of
a single zone system is the refrigerant piping. Table 6 lists the pipe length limits that must be followed in
the design of a Single Zone VAHU refrigerant pipe system.
Figure 29: LV120HCV, LV180HCV, LV240HCV, LV300HCV System Layout
Typical Indoor Unit
Unit = Feet
Max. Length = A
Max. Elevation = B
164
A
B
98
Outdoor Unit
Table 6: Single Zone VAHU Refrigerant Piping System Limitations
System Model Name
Pipe Length
(ELF = Equivalent
Length of Pipe in Feet)
Elevation
(All Elevation Limitations
are Measured in Actual
Feet)
Additional Refrigerant Needed (oz/ft)
REFRIGERANT SAFETY STANDARDS /
DEVICE CONNECTION LIMITATIONS
Outdoor Unit
164
A
B
98
Typical Indoor Unit
Longest total equivalent piping length
Shortest total equivalent piping length
Distance between fittings and indoor
or
outdoor units
No additional refrigerant
If outdoor unit is above indoor unit
If outdoor unit is below indoor unit
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
LVU120HCV
LVU180HCV, LVU240HCV, LVU300HCV
98.4 feet
16.4 feet
≥20 inches
24.6 feet
66 feet
66 feet
0.21
164 feet
16.4 feet
≥20 inches
24.6 feet
98 feet
98 feet
0.43
INTRODUCTION | 25