General Refrigerant Piping System Information; Refrigerant Safety Standards; Device Connection Limitations - LG LS090HSV5 Installation Manual

Single zone high efficiency standard wall mount
Hide thumbs Also See for LS090HSV5:
Table of Contents

Advertisement

Refrigerant Safety Standards

ASHRAE Standards 15-2010 and 34-2010 address refrigerant safety and the maximum allowable concentration of refrigerant in an occupied
space. Refrigerant will dissipate into the atmosphere, but a certain volume of air is required to safely dissipate the refrigerant. For R410A
refrigerant, the maximum allowable concentration of refrigerant is 26 lbs./1,000 cubic feet (Addendum L modified the RCL to 26) of occupied
spaces. Buildings with 24-hour occupancy are allowed half of that concentration.
If a single zone system develops a refrigerant leak, the entire refrigerant charge of the system will dump into the area where the leak occurs.
To meet ASHRAE Standards 15 and 34, the smallest room volume on the system must be calculated and compared to the maximum allow-
able concentration. Also consult state and local codes in regards to refrigerant safety.

Device Connection Limitations

A single-zone system consists of one outdoor unit and one indoor
unit. One of the most critical elements of a single-zone system is
the refrigerant piping. If the connection piping is not within allowable
limits, there will be reliability, performance, noise, and vibration
issues. The table below lists pipe length limits that must be followed
in the design of a Single Zone High Efficiency Wall Mount refrigerant
pipe system. Refer to the figure for maximum length and elevation of
piping.
Table 7: Single Zone High Ef ciency Refrigerant Piping System Limitations.
Model Numbers
Pipe Sizes
Pipe Length
(ELF = Equivalent Length
of pipe in Feet)
Elevation
(All Elevation Limitations
are Measured in Actual
Feet)
Additional Refrigerant Needed (oz/ft)
DEVICE CONNECTION LIMITATIONS
Vapor
Liquid
Standard Piping Length
Piping Length with No
Additional Refrigerant
Longest total equivalent
piping length
Shortest total equivalent
piping length
Distance between fittings
and indoor units or
outdoor units
If outdoor unit is above
indoor unit
If outdoor unit is below
indoor unit
Due to our policy of continuous product innovation, some speci cations may change without noti cation.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 26: Single Zone High Ef ciency Wall Mount System Layout.
Indoor Unit
A
Outdoor Unit
B
LS090HSV5
(LSN090HSV5/
(LSN120HSV5/
LSU090HSV5)
LSU120HSV5)
Ø3/8
Ø1/4
24.6
41
82
9.8
20 inches
49.2
49.2
0.22
A
Indoor Unit
LS120HSV5
LS180HSV5
(LSN180HSV5/
LSU180HSV5)
Ø3/8
Ø1/4
24.6
41
82
9.8
20 inches
49.2
49.2
0.22
Outdoor Unit
B
Ø5/8
Ø3/8
24.6
24.6
114.8
9.8
20 inches
49.2
49.2
0.38
23