General Refrigerant Piping System Information; Refrigerant Safety Standards; Device Connection Limitations - LG LGRED LH188HHV1 Installation Manual

Single-zone convertible mid-static ducted lgred system
Table of Contents

Advertisement

REFRIGERANT SAFETY STANDARDS /

DEVICE CONNECTION LIMITATIONS

Refrigerant Safety Standards
ASHRAE Standards 15-2010 and 34-2010 address refrigerant safety and the maximum allowable concentration of refrigerant in an occupied
space. Refrigerant will dissipate into the atmosphere, but a certain volume of air is required to safely dissipate the refrigerant. For R410A
refrigerant, the maximum allowable concentration of refrigerant is 26 lbs./1,000 cubic feet (Addendum L modified the RCL to 26) of occupied
spaces. Buildings with 24-hour occupancy are allowed half of that concentration.
If a single zone system develops a refrigerant leak, the entire refrigerant charge of the system will dump into the area where the leak occurs.
To meet ASHRAE Standards 15 and 34, the smallest room volume on the system must be calculated and compared to the maximum allow-
able concentration. Also consult state and local codes in regards to refrigerant safety.
Device Connection Limitations
A single-zone system consists of one outdoor unit and one indoor
unit. One of the most critical elements of a single-zone system is
the refrigerant piping. If the connection piping is not within allowable
limits, there will be reliability, performance, noise, and vibration
issues. The tables below lists pipe length limits that must be followed
in the design of a Single Zone LGRED Convertible Mid-Static Ducted
refrigerant pipe system. Refer to the figures for maximum length and
elevation of piping.
Table 11: Single-Zone LGRED Convertible Mid-Static Ducted
Pipe Length
(ELF = Equivalent Length of Pipe)
Elevation
(All Elevation Limitations are Measured in
Actual Feet)
Additional Refrigerant Needed (oz/ft)
28
Refrigerant Piping System Limitations.
System Model Name
Longest total equivalent piping length
Shortest total equivalent piping length
Distance between fittings and indoor
or outdoor units
Standard length (no add'l refrigerant)
If outdoor unit is above indoor unit
If outdoor unit is below indoor unit
©
Figure 22: Typical LH188HHV1, and LH248HHV1 System Layout.
Max Length = A
Max Elevation = B
Indoor unit
164
A
B
Outdoor unit
Unit = Feet
Outdoor unit
164
A
B
Indoor unit
LH188HHV1, LH248HHV1
164 feet
16.4
25 feet
98 feet
98 feet
0.43