Installation

Floor Protection

Floor Protection
Non-combustible material
(such as a hearth pad) is
required underneath your
stove.
Notice: Be careful to protect the bottom of the stove and floor surfaces when moving the stove. Bottom
edges of the stove may be sharp and can scratch surfaces.
2"
6"
6"
*This will satisfy safety standards for both USA and Canada
Notice: Clearances may only be reduced by means approved by the regulatory authority having jurisdiction.
The stove must be installed on a noncombustible floor, with proper floor
protection, or on a masonry hearth. When a clean out T-vent is installed on
the inside of a home, the floor protector must extend 2 inches beyond the
rear of the T-vent.
When stove is vented straight through the wall and the clean out T-vent is
on the exterior of the home, the minimum clearance is 2 inches from the
back of the stove to the wall.
It is necessary to install Ember Protection: a type 1 floor protector for this
stove.
The floor protector must be non-combustible material, extending beneath
the stove with a minimum of 6 inches (152mm) in front of the glass, and
6 inches (152mm) to both sides of the stove.
Non-combustible floor protection must extend 2 inches (51mm) beneath
the flue pipe of installed horizontal venting or under the top vent adapter
with vertical installation. CANADA REQUIRED, USA RECOMMENDED.
2"
6"
6"
9
6"
6"
comfortbilt.net