Installation

Floor Protection

The stove must be installed on a noncombustible floor, with proper floor protection, or on a masonry hearth.
When a clean out T-vent is installed on the inside of a home, the floor protector must extend 2 inches beyond
the rear of the T-vent.
When stove is vented straight through the wall and the clean out T-vent is on the exterior of the home, the
minimum clearance is 2 inches from the back of the stove to the wall.
Notice: Be careful to protect the bottom of the stove and floor surfaces when moving the stove. Bottom
edges of the stove may be sharp and can scratch surfaces.
It is necessary to install Ember Protection: a type 1 floor protector for this stove.
The floor protector must be non-combustible material, extending beneath the stove with a minimum of 6
inches (152mm) in front of the glass, and 6 inches (152mm) to both sides of the stove.
2"
6"
*This will satisfy safety standards for both USA and Canada
Notice: Clearances may only be reduced by means approved by the regulatory authority having jurisdiction.
Non-combustible floor protection must extend 2 inches (51mm) beneath the flue pipe of installed horizontal
venting or under the top vent adapter with vertical installation. CANADA REQUIRED, USA
RECOMMENDED.
6"
6"
9
2"
6"
6"
6"