Interface Overview - Carrier WeatherMaker 50KCQ A04 Series Installation Instructions Manual

Single package rooftop heat pump with puron r-410a refrigerant
Hide thumbs Also See for WeatherMaker 50KCQ A04 Series:
Table of Contents

Advertisement

S-BUS
TERMINALS
(1 AND 2)
Fig. 50 — S-Bus Sensor DIP Switches
Table 10 —
HH57AC081
TERMINAL
NUMBER
LABEL
1
S-BUS
2
S-BUS
Use Fig. 50 and Table 11 to set the DIP switches for the desired
use of the sensor.
Table 11 —
HH57AC081
DIP SWITCH POSITIONS FOR SWITCHES 1, 2, AND 3
USE
1
DA
OFF
RA
ON
OA
OFF
NOTE: When an S-Bus sensor is connected to an existing net-
work, it will take 60 minutes for the network to recognize and
auto-configure itself to use the new sensor.
During the 60 minute setup period, no alarms for sensor fail-
ures (except SAT) will be issued and no economizing function
will be available.
CO
Sensor Wiring
2
When using a CO
sensor the black and brown common wires
2
are internally connected and only one is connected to "IAQ
COM" on the W7220. Use the power from the W7220 to pow-
er the CO
sensor OR make sure the ground for the power sup-
2
plies are common. See Fig. 51 for CO
DIP
SWITCH
LABEL
DIP
SWITCHES
(3)
S-BUS
2 PIN SIDE
CONNECTOR
Sensor Wiring Terminations
TYPE
DESCRIPTION
S-BUS
Communications
S-BUS
(Enthalpy Control
Sensor Bus)
S-BUS
Communications
S-BUS
(Enthalpy Control
Sensor Bus)
Sensor DIP Switch
2
3
ON
OFF
OFF
OFF
OFF
OFF
sensor wiring.
2
CO
SENSOR
2
24V
ANALOG
OUT
1
POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
Fig. 51 — CO

INTERFACE OVERVIEW

This section describes how to use the EconoMi$er
face for:
Keypad and menu navigation
Settings and parameter changes
Menu structure and selection
User Interface
The user interface consists of a 2-line LCD display and a 4-button
keypad on the front of the economizer controller.
Keypad
Use the four navigation buttons (see Fig. 52) to scroll through
the menus and menu items, select menu items, and to change
parameter and configuration settings.
To use the keypad when working with menus:
Press the ▲ (Up arrow) button to move to the previous
menu.
Press the ▼ (Down arrow) button to move to the next
menu.
Press the
(Enter) button to display the first item in the
currently displayed menu.
Press the
(Menu Up/Exit) button to exit a menu's item
and return to the list of menus.
Fig. 52 — W7220 Controller Navigation Buttons
To use the keypad when working with Setpoints, System and
Advanced Settings, Checkout tests and Alarms:
1.
Navigate to the desired menu.
2.
Press the
(Enter) button to display the first item in the
currently displayed menu.
Use the ▲ and ▼ buttons to scroll to the desired
3.
parameter.
32
RED
L1
(HOT)
BLACK
L2
1
YELLOW
+
BROWN
ORANGE
GREEN
Sensor Wiring
2
®
user inter-

Advertisement

Table of Contents
loading

Table of Contents