Enthalpy Settings - Carrier WeatherMaker 50KCQ A04 Series Installation Instructions Manual

Single package rooftop heat pump with puron r-410a refrigerant
Hide thumbs Also See for WeatherMaker 50KCQ A04 Series:
Table of Contents

Advertisement

Table 17 — Enthalpy Operation with DCV (CO
DEMAND
OUTSIDE AIR
CONTROLLED
GOOD TO
VENTILATION (DCV)
ECONOMIZE
Below CO
set
2
Above CO
set
2
*With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
†With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2–O after the delay if the call for Y1–I and
Y2–I have not been satisfied.
ECONOMIZING
AVAILABLE
NOT AVAILABLE
TEMPERATURE
Table 18 — Single Enthalpy and Dual Enthalpy High Limit Curves
ENTHALPY
TEMP. DRY
CURVE
BULB (F)
ES1
80
ES2
75
ES3
70
ES4
65
ES5
60
HL
86

ENTHALPY SETTINGS

When the OA temperature, enthalpy and dew point are below the
respective set points, the Outdoor Air can be used for economiz-
ing. Figure 53 shows the new single enthalpy boundaries in the
W7220. There are 5 boundaries (set points ES1 through ES5),
which are defined by dry bulb temperature, enthalpy and dew
point.
Refer to Table 18 for ENTH CURVE set point values.
Y1-I
Y2-I
SPEED
Off
Off
No
On
Off
On
On
Off
Off
On
Off
Yes
On
On
Off
Off
No
On
Off
On
On
Off
Off
Yes
On
Off
On
On
Fig. 53 — Single Enthalpy Curve Boundaries
TEMP.
ENTHALPY
DEWPOINT (F)
(btu/lb/da)
60
28.0
57
26.0
54
24.0
51
22.0
48
20.0
66
32.4
Sensor) — 1 Speed Fan
2
FAN
Y1-O
Y2-O
High
0-v/Off
0-v/Off
High
24-v/On
0-v/Off
High
24-v/On
24-v/On
High
0-v/Off
0-v/Off
High
0-v/Off
0-v/Off
High
24-v/On
0-v/Off†
High
0-v/Off
0-v/Off
High
24-v/On
0-v/Off
High
24-v/On
24-v/On
High
0-v/Off
0-v/Off
High
0-v/Off
0-v/Off
DELAY*
High
0-v/Off†
24-v/On
POINT P1
TEMP. (F)
80
75
70
65
60
86
The W7220 calculates the enthalpy and dew point using the OA
temperature and humidity input from the OA enthalpy sensor.
When the OA temperature, OA humidity and OA dew point are
all below the selected boundary, the economizer sets the econo-
mizing mode to YES, economizing is available.
When all of the OA conditions are above the selected boundary,
the conditions are not good to economize and the mode is set to
NO.
39
OCCUPIED
VENTMIN
VENTMIN
VENTMIN
VENTMIN
VENTMIN to
Full-Open
VENTMIN to
Full-Open
VENTMIN to
VENTMAX
VENTMIN L to
VENTMAX
VENTMIN H to
VENTMAX
VENTMIN L to
VENTMAX
VENTMIN to
Full-Open
VENTMIN to
Full-Open
DUAL ENTHALPY
HIGH LIMIT
SINGLE ENTHALPY
P2 (T,RH)
P1
(T,RH)
ES4
ES3
ES2
ES5
POINT P2
HUMIDITY
TEMP. (F)
(%RH)
36.8
66.3
39.6
63.3
42.3
59.7
44.8
55.7
46.9
51.3
38.9
72.4
UNOCCUPIED
Closed
Closed
Closed
Closed
Closed to
Full-Open
Closed to
Full-Open
Closed
Closed
Closed
Closed
Closed to
Full-Open
Closed to
Full-Open
ES1
HL
HUMIDITY
(%RH)
80.1
80.0
81.4
84.2
88.5
80.3