Bosch D9412GV4 Installation And Operation Manual page 48

Hide thumbs Also See for D9412GV4:
Table of Contents

Advertisement

D9412GV4/D7412GV4/D7212GV4 | Installation and Operation Guide | 9.0
Table 13:
Switch 5 Settings for Line
Termination
Is a D8125 POPEX
Module connected?
No
Yes
Point DIP Switches
Each point connected to the D8128D is enabled
by closing the respective DIP switch, or disabled
by opening the DIP switch. For example, to
disable a device connected to the P3 Terminal
(Point 3), move DIP switch number 3 to the
OPEN position.
Use the point DIP switches to disable conflicting
points, such as when a D9210C Access Control
Module must be assigned to a point that falls
within the range of the D8128D OctoPOPIT. In
this example, a D9210C is assigned to Point 20.
On the same system, a D8128D OctoPOPIT is
assigned to Points 17 through 24. Moving the DIP
switch for Point 4 to the OFF position would
effectively disable Point 20, allowing normal
operation of the D9210C and the OctoPOPIT.
Through panel configuration the Point Source
prompt further protects from possible point
addressing conflicts. A point can be ZONEX,
Octo-input, SDI2 Wireless, or Door Point.
Terminate each OctoPOPIT sensor loop with a 1
kΩ EOL resistor. Attach a resistor even if you do
not enable the loop.
9.4.5
Mounting OctoPOPITs
The D8128D OctoPOPIT Module can be installed
in the enclosure with the control panel using
standard four-conductor 0.8 mm (22 AWG) wire,
or in a separate enclosure (Model D8103,
D8103A, or D8109) up to 61 m (200 ft.) from the
control panel using shielded (recommended)
standard four-conductor 0.8 mm (22 AWG) wire.
If using the D125B or D129, refer to the
Specifications section of the D8128D Installation
Guide (P/N: F01U070537) for cabling
requirements.
Bosch Security Systems, Inc. | 3/12 | F01U266054-01
Switch 5 Setting(s) on
D8128D OctoPOPIT(s)
Set Switch 5 of only one
D8128D to ON
Set Switch 5 of all
D8128Ds to OFF
For UL Listed systems, mount the D8128D in a
tamper-proof enclosure. To install OctoPOPITs in
the control panel's enclosure, complete the
following procedure. Use the D137 Mounting
Bracket to install OctoPOPITs in enclosures with
no module-mounting locations available.
1. Align the OctoPOPIT module using any of the
four mounting locations in the enclosure.
Refer to
Figure 2 on page 16.
2. Use the screws provided with the module to
secure it in the enclosure.
9.4.6
Wiring OctoPOPITs
Warning: Disconnect all power to the
control panel before beginning any
work with the internal components.
Serious injury could result from
electrical shock.
1. Power down the control panel:
a. Disconnect the positive (red) battery
lead at the battery.
b. Unplug the transformer.
A D8128D OctoPOPIT can be installed
up to 61 m (200 ft.) from the control
panel.
2. Connect the D8128D to the control panel
using either of the following methods:
Wire the D8128D to the terminal strip on
the side of the POPEX Module, or
Connect the D8128D using the
interconnect wiring connectors (P1 and
P2). Refer to Using Interconnect Wiring on
page 52.
Caution - AC induction: Avoid installing
Zonex data wires and Zonex input
(sensor loop) wires around any AC
conduit, wiring, or electrical devices
that emit fields of electromagnetic
interference (EMI).
Using the Terminal Strip
Refer to Table 14, Figure 17 on page 50, and
Figure 18 on page 51 when using the terminal
strip to connect the D8128D OctoPOPIT to the
control panel.