Bosch D9412GV4 Installation And Operation Manual page 29

Hide thumbs Also See for D9412GV4:
Table of Contents

Advertisement

D9412GV4/D7412GV4/D7212GV4 | Installation and Operation Guide | 5.0
Table 7:
Charging Status and Low Battery LEDs
LED
Type
Color
Charging Status
Yellow
LED
Yellow
Yellow
Yellow
Low Battery LED
Red
Red
Red
Red
Bosch Security Systems, Inc. | 3/12 | F01U266054-01
State
Action
Shows the charging status of the battery. Refer to Figure 8
on
page 27 for location.
Off
Battery is fully charged.
If the battery is missing, shorted, or reversed, the Charging
Status LED is off, but the red Low Battery LED is flashing.
On
Battery float charge is below 13.8 VDC. If AC is present, the
battery is charging.
Indicates the combined current draw from all outputs
exceeds 1.4 A. This is normal under alarm conditions for
non-fire systems with sirens or bells drawing more than 1.4
A. If the LED lights regularly for extended periods or does
not go out, check the current draw for devices connected to
the power outputs. Refer to Section 6.0 Power Outputs on
page 30 for instructions.
Flash once per
System is checking the battery.
minute
Shows the condition of the battery. Refer to Figure 8 on
page 27 for location.
Off
Battery is fully charged.
On
Battery voltage dropped to between 12.0 VDC and 11.8 VDC.
LED turns off when voltage reaches 13.7 VDC.
Flash
Battery is missing or shorted.
Power Supply
29

Advertisement

Table of Contents
loading

This manual is also suitable for:

D7412gv4D7212gv4

Table of Contents