Bosch PXI-CORE Edge controller User Manual page 15

Table of Contents

Advertisement

PXI-CORE Edge controller
Figure 4.1: Removing the press fit plug
2.
1
2
Notice!
i
IMPORTANT
Connect the ground of the power supply to the blue connection point (2).
Connect the +24 V to the red connection point (1).
3.
Bosch Security Systems B.V.
Use the supplied press fit plug, and connect the 24 VDC wiring to the appropriate slot of
the connector XD10, observing polarity:
Use only copper AWG 16 (1.5 mm
Observe the wiring color convention: red for + (1) and blue for - (2).
Remove wire isolation for about 5 mm before inserting the wires into the connector
XD10.
When inserting the wires, keep the push button of the push-in terminal pressed.
Release the push-in terminal to lock the wires in.
Use only wiring approved for temperatures of at least 60 °C.
When reinstalling the press fit plug to the device, align the bottom fit of the plug with the
bottom horizontal pins in the PXI-CORE edge controller. Align the connector obliquely.
Detailed installation procedures and instructions | en
2
) wiring.
User manual
15
2023-03 | V01 | F01U395004

Advertisement

Table of Contents
loading

This manual is also suitable for:

F.01u.395.004

Table of Contents