SUN2000-(50KTL-ZHM3, 50KTL-M3)
User Manual
Parameter
n with
limited
power
(%)
Shutdow
Shutdown at high feed-in
n at high
power
feed-in
power
1
Upper feed-in power
threshold for inverter
shutdown (kW)
High feed-in power duration
threshold for triggering
inverter shutdown (s)
Issue 01 (2022-07-29)
Description
Limitation mode
PV plant
Specifies the total maximum active power in the inverter cascading
capacity
scenario.
Maximum grid
Specifies the percentage of the maximum active power of the
feed-in power
grid-tied point to the PV plant capacity.
Maximum
Specifies the time for detecting power meter data. If the Dongle
protection time
does not detect any power meter data within the preset time, the
Dongle delivers the preset value of Active power output limit for
fail-safe for protection.
Power raising
Specifies the step for grid-tied power adjustment.
threshold
Power
Specifies the shortest interval for a single export limitation
adjustment
adjustment.
period
Active power
Specifies the derating value of the inverter active power by
output limit for
percentage. If the Smart Dongle does not detect any power meter
fail-safe
data or the communication between the Smart Dongle and the
inverter is disconnected, the Smart Dongle delivers the derating
value of the inverter active power by percentage.
Communication
In the inverter export limitation scenario, if this parameter is set to
disconnection
Enable, the inverter will derate according to the active power
fail-safe
derating percentage when the communication between the inverter
and the Smart Dongle is disconnected for a period longer than
Communication disconnection detection time.
Communication
Specifies the time for determining the communication
disconnection
disconnection between the inverter and the Smart Dongle. This
parameter is displayed when Communication disconnection
detection time
fail-safe is set to Enable.
The default value is 0. This parameter specifies the power threshold
of the grid-connection point for triggering inverter shutdown.
The default value is 20. This parameter specifies the duration
threshold of high feed-in power for triggering inverter shutdown.
Copyright © Huawei Technologies Co., Ltd.
to SDongle/SmartLogger.
Total power indicates export limitation of the total power at the
grid-tied point.
Single-phase power indicates export limitation of the power in
each phase at the grid-tied point.
The default value is Disable.
If this parameter is set to Enable, the inverter shuts down for
protection when the grid-connection point power exceeds the
threshold and remains in this condition for the specified time
threshold.
When High feed-in power duration threshold for triggering
inverter shutdown is set to 5. Shutdown at high feed-in