SUN2000-(50KTL-ZHM3, 50KTL-M3)
User Manual
No.
D
E
F
Note [1]: For details about meter operations, see
Guide,
DTSU666-H 100 A and 250 A Smart Power Sensor User
Note [2]: SUN2000MA V100R001C20SPC116 and later versions can connect to
DTSU666-HW and YDS60-80 power meter.
The cable specifications must comply with local standards.
Table 5-2 Cable description
No.
1
2
Issue 01 (2022-07-29)
Component
Description
Janitza-UMG103-CBM,
Janitza-UMG104,
GAVAZZI-EM340-DIN AV2 3 X S1 X,
REAL ENERGY
SYSTEM-PRISMA-310A,
Algodue-UPM209,
Mitsubishi-LMS-0441E, and
WEG-MMW03-M22CH
When the WEG-MMW03-M22CH
power meter is connected, set Baud rate
to 9600. When the
Mitsubishi-LMS-0441E power meter is
connected, set Parity mode to No
parity, and Baud rate to 9600.
SUN2000
Select a proper model as required.
SmartLogger
SmartLogger3000
Smart Dongle
Select a proper model as required.
DTSU666-H and DTSU666-H 250 A (50 mA) Smart Power Sensor Quick Guide
Cable
Type
DC input
Common PV cable in the
power
industry
cable
(Recommended model:
PV1-F)
AC
Outdoor
output
copper-core/aluminum-core
power
cable
cable
Copyright © Huawei Technologies Co., Ltd.
5 Electrical Connections
Source
Purchased from
Huawei
Purchased from
Huawei
Purchased from
Huawei
DTSU666-HW Smart Power Sensor Quick
Manual.
Recommended
Specifications
Conductor
cross-sectional area:
4–6 mm
2
Cable outer diameter:
5.5–9 mm
Conductor
cross-sectional area:
25-50 mm
2
outdoor
copper-core cable or
35-50 mm
2
outdoor
aluminum-core
and
Source
Prepare
d by
users
Prepare
d by
users
30