SUN2000-(50KTL-ZHM3, 50KTL-M3)
User Manual
Parameter
Grid
connectio
n with
limited
power
(kW)
Grid
connectio
Issue 01 (2022-07-29)
Description
Communication disconnection detection time.
Communication
Specifies the fail-safe detection time for the disconnection between
disconnection
the SUN2000 and the Smart Dongle.
detection time
This parameter is displayed when Communication disconnection
fail-safe is enabled.
Closed-loop
controller
Total power indicates export limitation of the total power at the
Limitation mode
grid-tied point. (When a single-phase meter is connected, only
Total power can be selected.)
Single-phase power indicates export limitation of the power in
each phase at the grid-tied point.
Maximum grid
Specifies the maximum active power transmitted from the grid-tied
feed-in power
point to the power grid.
Power
Specifies the shortest interval for a single export limitation
adjustment
adjustment.
period
Maximum
Specifies the time for detecting power meter data. If the Dongle
protection time
does not detect any power meter data within the preset time, the
Dongle delivers the preset value of Active power output limit for
fail-safe for protection.
Power raising
Specifies the step for grid-tied power adjustment.
threshold
Power
Specifies the shortest interval for a single export limitation
adjustment
adjustment.
period
Active power
Specifies the derating value of the inverter active power by
output limit for
percentage. If the Smart Dongle does not detect any power meter
fail-safe
data or the communication between the Smart Dongle and the
inverter is disconnected, the Smart Dongle delivers the derating
value of the inverter active power by percentage.
Communication
In the inverter export limitation scenario, if this parameter is set to
disconnection
Enable, the inverter will derate according to the active power
fail-safe
derating percentage when the communication between the inverter
and the Smart Dongle is disconnected for a period longer than
Communication disconnection detection time.
Communication
Specifies the time for determining the communication
disconnection
disconnection between the inverter and the Smart Dongle. This
parameter is displayed when Communication disconnection
detection time
fail-safe is set to Enable.
Closed-loop
controller
Copyright © Huawei Technologies Co., Ltd.
If multiple SUN2000s are cascaded, set this parameter to
SDongle/SmartLogger.
If there is only one SUN2000, set this parameter to Inverter.
For a single inverter, set Closed-loop controller to Inverter.
For multiple inverters, Closed-loop controller can only be set
7 Man-Machine Interaction
60