Setting up the
communication
gateway
1.
2.
3.
2023/03/03
CPU and PC are connected with an Ethernet cable.
In the Automation Builder device tree right-click "PLC_AC500_V2".
Select "Communication Settings".
Keep the default value in the IP address of the CPU or type in the current IP address, if
differs.
The standard (default) IP address of the port ETH1 is: 192.168.0.10
The standard (default) IP address of the port ETH2 is: 192.168.1.10
3ADR010649, 3, en_US
Example project for central I/O expansion > Setting up the communication gateway
Getting started with example projects
33