Fig. 16 Cable Length Output - Beckhoff EK1914 Operating Manual

Twinsafe bus coupler with 2 fail-safe inputs and 2 fail-safe outputs
Table of Contents

Advertisement

Installation
7.4.6.2
Permitted cable length - outputs
Fig. 16: Cable length output
When connecting a single actuator via its own continuous cabling (or via a sheathed cable), the maximum
permitted cable length is 100 m.
Route the signal cable separately
Route signal cable separately from potential sources of interference. Possible sources of interference are,
for example, motor supply cables or power cables with 230 V
large as possible.
Interference from cables routed in parallel can influence the signal shape of the test pulses and thus cause
diagnostic messages. Possible diagnostic messages are, for example, sensor errors.
The following illustrations show correct and incorrect signal routing. Observe the illustration legend.
36
NOTE
. Keep the distance between the cables as
AC
Version: 2.0.0
EK1914