Parameter
4.3 Configuration control (option handling)
Data record of the example
The following table shows the structure of the control data record for the above example.
Table 4- 10
Data record for example "Combining configurations"
Byte
Element
0
Block length
1
Block ID
2
Version
3
Version
4
Slot 0
5
Slot 2
6
Slot 3
7
Slot 4
8
Slot 5
9
Slot 6
10
Slot 7
11
Slot 8
12
Slot 9
13
Slot 10
14
Slot 11
15
Slot 12
16
Slot 13
30
Code
Code
configuration 1
configuration 2
17
196
3
0
00000000
00000000
B
00000010
00000010
B
00000011
00000011
B
00000100
00000100
B
00000101
00000101
B
01111111
00000110
B
01111111
00000111
B
00000110
00001000
B
00000111
00001001
B
00001000
00001010
B
01111111
00001100
B
01111111
00001101
B
00001001
00001011
B
Explanation
Header
The configured slot 0 is the real slot 0.
B
The configured slot 2 is the real slot 2.
B
The configured slot 3 is the real slot 3.
B
The configured slot 4 is the real slot 4.
B
The configured slot 5 is the real slot 5.
B
The configured slot 6 does not exist (configuration 1).
B
The configured slot 6 is the real slot 6 (configuration 2).
The configured slot 7 does not exist (configuration 1).
B
The configured slot 7 is the real slot 7 (configuration 2).
The configured slot 8 is the real slot 6 (configuration 1).
B
The configured slot 8 is the real slot 8 (configuration 2).
The configured slot 9 is the real slot 7 (configuration 1).
B
The configured slot 9 is the real slot 9 (configuration 2).
The configured slot 10 is the real slot 8 (configuration 1).
B
The configured slot 10 is the real slot 10 (configuration 2).
The configured slot 11 does not exist (configuration 1).
B
The configured slot 11 is the real slot 12 (configuration 2).
The configured slot 12 does not exist (configuration 1).
B
The configured slot 12 is the real slot 13 (configuration 2).
The configured slot 13 is the real slot 9 (configuration 1).
B
The configured slot 13 is the real slot 11 (configuration 2).
IM 155-5 PN ST interface module (6ES7155-5AA00-0AB0)
Manual, 08/2013, A5E03612323-02