Burner Operating Sequence (Light Oil Operation) - Riello RLS 810/E FGR Installation, Use And Maintenance Instructions

Dual fuel gas oil/ gas burner
Table of Contents

Advertisement

4.14

Burner operating sequence (LIGHT OIL OPERATION)

CPI/POC
X07
X06
X10
X08
X20+X21
X32+X34
X33
X4
X01
X02
X03
X25
X26
X05
S9782
CPI= Close Position Indicator
POC= Prove Of Closure
(3)
Oil irrelevance time P323, has an effect on the oil safety chain and on the minimum oil pressure when the air valve is opened.
Key to layout (Fig. 8)
Any condition
t1
Waiting time for safety circuits consent
(boiler fuel)
t2
Opening time of the gas valve (with
sealing control active)
t3
Servomotor opening time
t4
Activation time FGR servomotor
t5
Pre-purge time
t6
Pre-ignition time
t7
Ignition flame safety time
t8
Flame stabilization time
nd
t9'
Safety time 2
t10
Modulation phase
t11
Adjustment time
t12
Opening time of the gas valve (with
sealing control active)
t13
Post-purge time
t15
Post-combustion time
t16
Checking time for flame extinction
t17
Checking time for gas valve (with seal-
ing control active)
Technical description of the burner
adjustable
adjustable
adjustable
stage
adjustable
adjustable
Key to layout (Fig. 8)
X01
1st meter oil valve
X02
2nd meter oil valve
X03
3th meter oil valve
X04
Ignition transformer
2.4 s
X05
Oil pressure > min.
X06
oil safety circuit
30/60 s
X07
Boiler safety circuit
0 - t5
X08
Air pressure switch
X10
Burner ON
X20+X21 Flame signal
X25
Fan ON
3 s
X26
Oil pump
X32
Air servomotor
X33
Fuel servomotor
3 s
X34
FGR servomotor (disable)
3 s
5 s
30 s
Tab. I
15
GB
Fig. 8
20171988