Firing Rates; Test Boiler - Riello RLS 810/E FGR Installation, Use And Maintenance Instructions

Dual fuel gas oil/ gas burner
Table of Contents

Advertisement

4.7

Firing rates

The MAXIMUM OUTPUT is chosen from within the diagram area
(Fig. 2).
The MINIMUM OUTPUT must not be lower than the minimum
limit of the diagram:
GAS
RLS 810/E FGR
OIL
NOTE:
OIL OPERATION: max 5 kW for smoke index <1.
4.8

Test boiler

The burner/boiler combination does not pose any problems if the
boiler is EC approved and its combustion chamber dimensions
are similar to those indicated in the diagram (Fig. 3).
If the burner must be combined with a boiler that has not been EC
approved and/or its combustion chamber dimensions are clearly
smaller than those indicated in the diagram, consult the manufac-
turer.
20171988
Technical description of the burner
1080 kW
1650 kW
Tab. F
Thermal power – kW
10
GB
The firing rate value (Fig. 2) has been obtained
considering an ambient temperature of 20 °C, an
atmospheric pressure of 1013 mbar (approx. 0 m
a.s.l.), and with the combustion head adjusted as
WARNING
shown on page 22.
The firing rates were set in relation to special test boilers, accord-
ing to EN 676 regulations.
In Fig. 3 you can see the diameter and length of the test combus-
tion chamber.
Example:
Output 5000 kW - diameter 100 cm - length 5 m
20176363
Fig. 2
20057548
Fig. 3