15.4 MAINTENANCE

15.4.1 Weekly Exercise – Record pump
shutoff pressure and engine RPM.
Maintain weekly readings in a log for
future reference.

15.5 TROUBLESHOOTING

15.5.1 Powerview Gauge Diagnostics
 In the event of the VSPLC or
VSSLC pressure transmitter
(See Figure #4, Detail "A")
failure, a warning light and
message will be displayed on the
Powerview on the engine
instrument panel.
 A full listing of Powerview
Gauge diagnostic codes and
means of correction can be
found within the engine
Operator's Manual, listed in
Section 5 of this document.
 Additionally, a low suction
pressure alarm will be activated
via the LSP terminal
following conditions:
o Engine has reduced
o Suction pressure is 1 psi,
15.5.2 Contact Information
www.clarkefire.com
 Phone (513) 771-2200 Ext. 427
 Fax (513) 771-5375
 E-Mail:
parts@clarkefire.com
under the
speed to the minimum
operating speed
(1100rpm) and suction
pressure is 1 psi, or
further, below set
pressure for more than 5
seconds.
or further, below set
pressure for more than
15 seconds