4) Toggle down the list of menu options and
highlight "Soft Start", then press the "Enter"
key.
5) The next screen will display one choice,
"Request Soft Start". Press the "Enter" key.
6) The next screen will allow initiation of Soft
Start or the choice to cancel the process. To
proceed with the Soft Start, crank and start the
engine with one of the Manual Crank switches
on the front of the panel.
7) The engine will start and run at 1100 rpm until
the "Confirm" key is pressed. Once the
"Confirm" key is pressed, the engine will
increase speed at the rate of 10 rpms per
second until it reaches rated speed.
1 - PowerView Gauge
2 - Momentary Display On Switch
3 - Automatic/Manual Mode Selector Switch
4 - ECM Selector Switch
5 - Manual Mode Indicator Warning Light

2.6.2 To Stop Engine

If engine is started from main pump controller use
main pump controller to stop the engine.
If engine is started from engine gauge panel: Lift and
hold MANUAL STOP SWITCH, until engine stops.
Close cooling system manual by-pass valve if opened.
Note: This is NOT the switch to use during cycle-
crank testing. This switch will allow the engine to
briefly start, before stopping the engine.
IMPORTANT: DO NOT leave the MODE
SELECTOR switch in the MANUAL RUN position
during AUTOMATIC operation. (The controller will
be unable to stop the engine and DAMAGE MAY
RESULT)
Figure #8
6 - Alternate ECM Indicator Warning Light
7 - Manual Stop Switch
8 - Manual Crank Switch – Battery #1
9 - Manual Crank Switch – Battery #2
10 – Service Tool Connector
11 – PLD Sensor Harness Connector
17