Installing A Liquid Cooling Cold Plate - Dell PowerEdge C6620 Installation And Service Manual

Table of Contents

Advertisement

NOTE:
Ensure latching features on processor retaining clip and cold plate are aligned during assembly.
NOTE:
The numbers on the image do not depict the exact steps. The numbers are for representation of sequence.
Figure 86. Installing the cold plate onto the processor
Next steps
1.
Install a liquid cooling cold plate with leak
2. Follow the procedure listed in

Installing a liquid cooling cold plate

Prerequisites
1. Follow the safety guidelines listed in
2. Follow the procedure listed in
Steps
1. Set the Anti-Tilt wires to the unlocked position on the cold plate (inward position).
2. Align the pin 1 indicator of the cold plate to the system board, and then place the cold plate assembly unto the processor
sockets.
CAUTION:
To avoid damaging to the tubes, do not press down on the tubes.
NOTE:
Ensure that the processor and cold plate is held parallel to the system board to prevent damaging the
components.
110
Installing and removing system components
sensor.
After working inside your
Safety
instructions.
Before working inside your
system.
system.