SYSCW-AR R513A POWER SUPPLY MUST BE SWITCHED OFF BEFORE STARTING WORK IN THE ELECTRIC CONTROL 1. GENERAL RECOMMENDATIONS The purpose of this Manual is to provide users with instructions for installing, commissioning, using and maintaining the units. It also contains instructions on starting up the machine as well as recommendations to avoid bodily injury and risks of damage to the device during its operation.
4 SYSCW-AR R513A 1.3. EQUIPMENT SAFETY DATA Safety data R513A Toxicity level Low. Dermal contact with the rapidly evaporating liquid can cause frostbite to the tissue. In the event In contact with the skin of contact with the liquid, warm the frozen tissue with water and notify a physician. Remove contaminated clothing and shoes.
For technical questions, work under warranty, commissioning, a manufacturer’s visit or repair quotations. Our technical support and after-sales service hotline can be reached on: (0)891 700 407 in France ² support@systemair.fr for export customers ² 5. PRESENTATION The SYSCW-AR units are produced in compliance with state-of-the-art design and manufacturing standards.
6 SYSCW-AR R513A 6. CONTENTS OF PACKAGE Package contents: appliance installation manual 6.1. OPTIONAL ACCESSORIES Remote control On opening the box, check that all of the accessories required for installation are present. 7. DIMENSIONS SEE APPENDIX 8. HANDLING 8.1. NET WEIGHT MODELS STANDARD LOW HEIGT...
: Electrical connection right side : Electrical connection left side Acoustic : Standard Low Noise : Extra low noise Brand Systemair Fan type : Ventilateur moteur AC : Ventilateur moteur EC : G2 filter - bottom - dessous (fixed Air filter...
SYSCW-AR R513A 9.5. REFRIGERATION SPECIFICATIONS 9.5.1. REFRIGERANT CIRCUIT DIAGRAM SEE APPENDIX 9.5.2. REFRIGERANT CHARGE Caution This equipment contains fluorinated gas with greenhouse gas effects covered by the Kyoto agreement. The type and quantity of refrigerating fluid per circuit are indicated on the product plate. The installer and end user will get informed on local environmental regulations for the installation, operation and disposal of the equipment ;...
12 SYSCW-AR R513A 10. INSTALLATION Caution The unit is not designed to withstand weights or stresses from adjacent equipment, pipe work or constructions. Any foreign weight or stress on the unit structure could lead to a malfunction or damage, which could prove hazardous to personnel and property. In such an event, the warranty shall be voided.
SYSCW-AR R513A 10.2. CLEARANCE 70mm 70mm 70mm 70mm 10.3. UNIT INSTALLATION 10.3.1. CONNECTION POSITIONS Factory-configured water connections are available in 4 different positions: right side left side ² ² Water outlet Water outlet Condensates outlet Water inlet Water inlet Condensates outlet rear panel underneath (option not available when the air ²...
14 SYSCW-AR R513A 10.3.2. CABINET REMOVAL Caution When removing cabinet do not pull or lift it up by the discharge grilles, to avoid any damages on articulated fasteners of the access doors. No tools are required to remove the casing. You just have to lift it up slightly to release the olive-shaped attachment studs from the buttonholes.
SYSCW-AR R513A 10.4. AERAULIC ADJUSTEMENT 10.4.1. MODEL SYSCW-AR 07R - EC MOTOR Air flow (m 10.4.2. MODEL SYSCW-AR 09R - EC MOTOR Air flow (m 11. UNCLAMPING THE COMPRESSOR Caution Before the first start-up the compressor transport clamping be removed.
16 SYSCW-AR R513A 12. HYDRAULIC LINKS Caution THE WARRANTY DOES NOT COVER DAMAGE DUE TO CORROSION RESULTING FROM ELECTROLYTIC PHENOMENA. 12.1. WATER QUALITY The water must be analyzed; the hydraulic network system installed must include all elements necessary for water treatment: filters, additives, intermediate exchangers, drain valves, vents, check valves, etc., according to the results of the analysis.
SYSCW-AR R513A 12.2. RECOMMENDATIONS FOR HYDRAULIC CONNECTIONS 1. It is recommended that all units are connected to a water supply and return pipe system of the Tickelman Loop type. The Tickelman Loop system is self-balancing and thus only requires manual balancing if a large number of units with different flow and pressure loss characteristics are connected to a single hydraulic loop.
18 SYSCW-AR R513A 8. Use steel, copper or P.V.C. pipes for the condensates drainage pipe. Each unit is supplied with a connector for condensates drainage. 9. No point of the condensates drainage pipe work should be located above the level of one of the units’...
20 SYSCW-AR R513A 14.1. UNIT POWER SUPPLY The position of the electrical connections depends on the type of appliance and the chosen options. The electrical connections can be made either on the connection box on the right hand side or on the top of the appliance, or on a remote terminal box located on the left hand side of the appliance.
SYSCW-AR R513A 14.2. REMOTE CONTROL 14.2.1. WALL MOUNTING Separate the remote control from its rear plate. Checking support bracket : Ensure that the wall surface is completely flat at the point where you wish to install the remote control, as it is important that the remote control is not twisted on installation, because any bending could lead to the...
Page 24
22 SYSCW-AR R513A SYSCW-AR - MASTER/SLAVES 15 regulators maximum Lmax = 100 M Lmax = 1 000 M Caution Master/slaves operation requires the allocation of a specific address to each controller. This addressing occurs by connecting a POL871 or POL895 display to the "BSP-BUS” port of each controller.
SYSCW-AR R513A 15. REGULATION SYSCW-AR units are fitted with an electronic control system. It provides the command, control and alarm functions. 15.1. ORDER OF PRIORITY FOR CONTROL SYSTEMS The integrated regulator in the SYSCW-AR can be controlled by various interfaces and systems. The order of priority for each drive system is as follows: The all remote control: the commands are given by the user directly on the unit Digital inputs: the client can transmit...
24 SYSCW-AR R513A 15.2.2. SCREEN Icons Meanings AUTO 23.5 SYSCW-AR off °C Hourly programming active 05:30 AUTO month year Operation in Eco mode Operation in Comfort mode COOL mode HEAT Mode Auto-changeover mode. The control displays the active heat control mode. Ventilation only When the unit is off, the temperature displayed is that measured by the control’s internal 23.5...
SYSCW-AR R513A 15.2.4. SCHEDULING Scheduling is used to select the unit activation and shutdown times. Each day is broken down into 6 time slots set by Selected time slot mode A start time ² A state: ON or OFF ² 05:30 Time slot start ...
26 SYSCW-AR R513A 16. FINAL TASKS Place the plugs back on the valves and check that they are properly tightened. If needed, fix the cables and the pipes on the wall with clamping collars. Operate the SYSCW-AR in the presence of the user and explain all functions. Show him how to remove, clean and place back the filters.
SYSCW-AR R513A 17.1. COMMISSIONING After performing all the above-mentioned checks, proceed with creating a demand for Cooling and Heating or vice versa. 17.1.1. DEMAND FOR COOLING 1. With the key on the control module, select COOL mode and then set the minimum temperature with the UP and DOWN arrows.
28 SYSCW-AR R513A 18. MAINTENANCE Maintenance in accordance with our instructions will prolong the service life of your SYSCW-AR : Better refrigeration performance ² Reduced power consumption ² Accidental component breakage prevention ² Prevention of heavy, late, and expensive maintenance work ²...
SYSCW-AR R513A 18.1.5. AIR FILTER In order for the installation to operate correctly, it is essential to regularly clean the air filter located in the intake of the indoor unit. When clogged, the filter reduces the air flow through the heat exchanger of the indoor unit, which in turn reduces the efficiency of the installation and inhibits the cooling of the fan motor.
30 SYSCW-AR R513A 18.2. FAULT FINDING 18.2.1. NEITHER THE FAN NOR THE COMPRESSOR OPERATE 1. The system is in alarm mode when the mains power supply is switched on. Check the points mentioned in § ALARM CODES, page 31 for diagnosis. 2.
SYSCW-AR R513A 18.2.6. APPEARANCE OF ABNORMAL NOISES AND VIBRATIONS IN THE CASING 1. Check that the turbine is not rubbing against the scroll and that the latter is not damaged. Replace as required. 2. Check that the turbine has not worked loose on its shaft. Centre the turbine and tighten it as required.
32 SYSCW-AR R513A 19. WARRANTY CLAIM - MATERIAL RETURN PROCEDURE Equipment must not be returned without the permission of our After Sales Department. To return the equipment, contact your nearest sales office (Refer to the § TECHNICAL SUPPORT AND AFTER- SALES SERVICE HOTLINE, page 5) and ask for a "return form".
Page 45
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO HYDRAULIC CONNECTIONS SYSCW-AR R513A VC BA / SYSCW-AR R513A VN BA SYSCW-AR R513A VC FA / SYSCW-AR R513A VN FA SYSCW-AR R513A...
Page 46
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO SYSCW-AR R513A VCL BA / SYSCW-AR R513A VNL BA SYSCW-AR R513A VCL FA / SYSCW-AR R513A VNL FA XII SYSCW-AR R513A...
Page 47
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO REFRIGERANT CIRCUIT DIAGRAM SCHEMA DU CIRCUIT FRIGORIFIQUE KÄLTEKREISLAUFDIAGRAMM SCHEMA DEL CIRCUITO REFRIGERANTE ESQUEMA DEL CIRCUITO FRIGORIFÍCO Deutsch English Français C1 : Compressor C1 : Compresseur C1 : Verdichter 1 RV : Cycle reversal valve RV : Vanne inversion de cycle...
Page 48
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO WATER R513A FILTER XIV SYSCW-AR R513A...
Page 49
APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO WIRING DIAGRAM SCHEMAS ELECTRIQUES STROMLAUFPLANS SCHEMA ELETRICO ESQUEMA ELECTRICO TAKE CARE! These wiring diagrams are correct at the time of publication. Manufacturing changes can lead to modifications. Always refer to the diagram supplied with the product. ATTENTION Ces schémas sont corrects au moment de la publication.
Page 56
As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos. Systemair AC SAS Route de Verneuil 27570 Tillières-sur-Avre FRANCE & : +33 (0)2 32 60 61 00 6 : +33 (0)2 32 32 55 13...
Need help?
Do you have a question about the SYSCW-AR 07R and is the answer not in the manual?
Questions and answers