Tzidc-120 - Ex Relevant Specification; Atex / Ukex - 'Ex I' Type Of Protection - ABB TZIDC-110 Operating Instruction

Digital positioner
Hide thumbs Also See for TZIDC-110:
Table of Contents

Advertisement

20
TZIDC-110, TZIDC-120 DIGITAL POSITIONER | OI/TZIDC-110/TZIDC-120-EN REV. H
... 2 Use in potentially explosive atmospheres
TZIDC-120 – Ex relevant specification
Note
The values indicated here are taken from the respective
certificates. Always observe the specifications and supplements
in the explosion protection certificates.
ATEX / UKEX – 'Ex i' type of protection
Ex-marking
Ex marking
Marking
II 2 G Ex ia IIC T6, T4...T1 Gb
II 2 G Ex ib IIC T6, T4 ...T1 Gb
Type examination
TÜV 04 ATEX 2702 X
certificate (ATEX)
Certificate (UKEX)
EMA22UKEX0032X
Type
Intrinsically safe equipment
Device class
II 2G
Standards
EN 60079-0, EN 60079-11
Temperature data
Temperature class
Ambient temperature Ta
T4 to T1
−40 to 85 °C
T6
−40 to 40 °C*
Electric Data
With the 'Intrinsic safety Ex i IIC' type of protection, only for
connection to a certified FISCO power supply unit or a barrier,
i.e., a power supply unit with maximum values according to the
following tables:
Connection to a barrier or power supply unit
Current circuit (terminal)
Electrical information (maximum values)
Signal circuit
Voltage:
(+11 / −12)
Current:
Power:
L
, C
i
Characteristic
curve:
Connection to a FISCO power supply unit
Current circuit (terminal)
Electrical information (maximum values)
Signal circuit
Voltage:
(+11 / −12)
Current:
Power:
L
, C
i
Characteristic
curve:
24 V
250 mA
1.2 w
Negligible
i
rectangular
17.5 V
17.5 V
380 mA
360 mA
5.32 w
2.52 W
Negligible
i
rectangular
trapezoidal
Current circuit (terminal)
Electrical information (maximum values)
Feedback on the actuator
For maximum values, see EU-Type examination
position using proximity
certificate PTB 00 ATEX 2049 X Pepperl & Fuchs
switches, (Pepperl & Fuchs
Type 2 proximity switches
SJ2-SN)
(Limit1: +51 / −52),
(Limit2: +41 / −42)
Local communication
Only for connection to a programming device
interface (LCI)
using an ABB LCI adapter (Um ≤ 30 V DC) outside
the hazardous area.
Special conditions
Permissible for the 'Natural gas version' only:
The positioner TZIDC-120 may be operated as a power
supply only with gases of Group IIA and temperature class
T1 outdoors or inside of buildings with sufficient
ventilation.
The supplied gas must be free of air and oxygen to
prevent the forming of a hazardous atmosphere.
Exhaust gas must always be discharged outside.
The equipment may only be used as a II 2D type device
TZIDC-120 in areas where the level of mechanical danger is
"low".
For TZIDC-120 electrostatic charging caused by propagating
brush discharge should be prevented when the device is used
for applications involving combustible dust.
For devices that are operated in an intrinsically safe manner,
cable and wire entries should be used that meet the
requirements of EN 60079-11 for Category II 2G as well as the
ambient temperature range.
The 'local communication interface' (LCI) of the TZIDC-120
may only be operated at U
area.
≤ 30 V DC outside the hazardous