ABB TZIDC-110 Operating Instruction page 17

Digital positioner
Hide thumbs Also See for TZIDC-110:
Table of Contents

Advertisement

TZIDC-110, TZIDC-120 DIGITAL POSITIONER | OI/TZIDC-110/TZIDC-120-EN REV. H
Maintenance or replacement works are to be carried out by
qualified personnel only, i.e. personnel qualified according to
TRBS 1203 or similar.
Only such auxiliary components may be used in explosive
atmospheres which meet all requirements of European and
national directives and legislation.
Maintenance works that require a dismantling of the system
shall only be performed if the atmosphere is Ex-free. If that is
not possible, however, the usual precautions have to be
ensured according to local regulations.
Components shall only be replaced by original spare parts
which are therefore approved for the use in ex- plosive
atmospheres.
Inside the Ex-atmosphere the equipment has to be cleaned
regularly. The intervals are to be defined by the user in
compliance with the environmental conditions present at the
place of operation.
After maintenance and repair works have been performed, all
barriers and notes removed for that purpose have to be put
back in their original place.
The flameproof joints differ from the tables of IEC 60079-1
and should only be repaired by the manufacturer.
Activity
Activity
inspection
every 3 months
Visual inspection of
positioner for intactness,
removal of dust
settlements
Check of electrical system
for intactness and
functionality
Check of entire system
Fault elimination
No changes or modifications may be performed on equipment
that is operated in conjunction with explosive atmospheres.
Such equipment shall only be repaired by expert personnel
trained and authorized to do so.
Visual
Close inspection
Detailed
every 6 months
inspection every
12 months
User's responsibility
Warning markings
''TO PREVENT IGNITION OF FLAMMABLE GASES OR VAPORS,
DO NOT REMOVE COVER WHILE CIRCUITS ARE LIVE''
"POUR ÉVITER L'INFLAMMATION DE GAZ OU DE VAPEURS
INFLAMMABLES, NE PAS RETIRER LE COUVERCLE LORSQUE
LES CIRCUITS SONT SOUS TENSION."
"FOR PROPER SELECTION OF CABLES SEE ELECTRICAL
INSTALLATION INSTRUCTIONS IN THE MANUAL"
"POUR LA SÉLECTION APPROPRIÉE DES CÂBLES, VOIR LES
INSTRUCTIONS D'INSTALLATION ÉLECTRIQUE DANS LE
MANUEL"
If the equipment was tested according to the exception of table
5 from FM class 3615, the label shall contain the statement:
''SEAL ALL CONDUITS WITHIN 18 INCHES''
"SCELLER TOUS LES CONDUITS À MOINS DE 18 POUCES"
Equipment supplied with a factory-installed conduit seal shall be
marked with the words:
''FACTORY SEALED, CONDUIT SEAL NOT REQUIRED''
"SCELLÉ EN USINE, JOINT DE CONDUIT NON REQUIS"
17