Special conditions
Devices must only be connected to circuits in zone 2 if they
are suitable for operation in zone 2 potentially explosive
atmospheres and for the conditions prevailing at the
installation location (manufacturer's declaration or
certificate from an inspection authority).
For the 'Feedback on the actuator position using proximity
switches' circuit, measures outside of the device must be
implemented to prevent an up-scale of the rated voltage by
more than 40 % in the event of transient disturbances.
It is only permissible to connect, disconnect, and switch live
circuits during installation or maintenance, or for the
purpose of carrying out repairs. Comment: It is considered
very unlikely that a potentially explosive atmosphere would
be present in zone 2 at the same time that installation or
maintenance/repair work was being carried out.
Only non-flammable gases may be used for the pneumatic
auxiliary power.
Only use suited cable entries that meet the requirements of
EN 60079-15.