TZIDC-110, TZIDC-120 DIGITAL POSITIONER | OI/TZIDC-110/TZIDC-120-EN REV. H
IECEx – 'Ex na' and 'Ex ec' type of protection
Ex-marking
IECEx Ex ec
Marking
Ex ec IIC T6 resp. T4...T1 Gc
Type Examination Test
IECEx TUN 04.0015X
Certificate
Type
Increased safy „e"
Standards
IEC 60079-0, IEC 60079-7
IECEx Ex nA
Marking
Ex nA IIC T6 resp. T4...T1 Gc
Type Examination Test
IECEx TUN 04.0015X
Certificate
Type
Type of protection „n"
Standards
IEC 60079-0, IEC 60079-15
Temperature data
Temperature class
Ambient temperature Ta
T4 to T1
−40 to 85 °C
T6
−40 to 50 °C
Electric Data
Current circuit (terminal) Electrical information (maximum values)
Signal circuit
U = 9 to 32 V DC
(+11 / −12)
I = 10.5 mA
Feedback on the actuator
For maximum values, see EU-Type examination
position using proximity
certificate PTB 00 ATEX 2049 X Pepperl & Fuchs
switches,
Type 2 proximity switches
(Pepperl & Fuchs SJ2-SN)
(Limit1: +51 / −52),
(Limit2: +41 / −42)
Local communication
Only for connection to a programming device
interface (LCI)
using an ABB LCI adapter (Um ≤ 30 V DC) outside
the hazardous area.
Special conditions
In the case of TZIDC-110, TZIDC-120, the following shall apply for
safe use in the Ex 'ec IIC' type of protection:
Only devices that are suited for operation in hazardous
areas of Zone 2 and the conditions prevailing at the place
of use may be connected to circuits in Zone 2
(manufacturer's declaration or certificate from the test
center).
For the 'Mechanical digital feedback with Pepperl & Fuchs
SJ2-SN proximity switches' circuit, external measures
must be implemented outside of the device to prevent
the rated voltage from being up-scaled by more than
40 % in the event of transient disturbances.
It is only permissible to connect, disconnect, and switch
live circuits during installation or maintenance, or for the
purpose of carrying out repairs.
Note
It is considered very unlikely that a potentially hazardous
atmosphere would be present in Zone 2 at the same time
that installation or maintenance or repair work was being
carried out.
Only non-flammable gases must be used for pneumatic
power supply.
Only cable entries may be used that suit the requirements
of EN 60079-7 or EN 60079-15.