5.6

Securing the burner to the boiler

Prepare a suitable lifting system to secure the
burner to the boiler.
 Put on the flange 1)(Fig. 7) the screw 2) and two nuts 3).
 It is necessary that the insulating gasket 5)(Fig. 10) is placed
between the boiler door and the burner flange.
If necessary, the insulating gasket can be modified as shown
in Fig. 8.
 Fix the flange 1) to the boiler door 4) using screws 2) and (if
necessary) the nuts 3) interposing the insulating gasket 5).
 Verify that the installed burner is lightly leaned towards the
button (Fig. 9).
 Insert the burner tube through the flange and push to ensure
full insertion. With the burner collar fully inserted into the
flange the O-ring will form a seal. Fix the securing nut 3)
onto the bolt 2)(Fig. 7).
The seal between burner and boiler must be
airtight.
WARNING
1
3
Installation
2
E9022
Fig. 7
1
2
D8058
13
D5242
D5572
4
3
5
2
GB
Fig. 8
Fig. 9