Richmond GTR064 Quick Start Manual

Movement issue
Hide thumbs Also See for GTR064:

Advertisement

Gate does not move when remote button is pressed
Gate does not stop at the limit switch or does not soft close
Gate does not fully open or close.
Gate opens but cannot close.

Possible Causes

** Any works done to the motor must be completed whilst the power is off, and the motor is unplugged **
1. Remotes are not operating, or are not paired correctly
2. The gate direction setup is incorrect
3. The magnets are not positioned correctly
4. The motor output force is too low
5. Photocell settings or mounting is incorrect

Step-by-Step Troubleshooting

*If you are uncomfortable or unsure about performing any of these tests please contact Richmond Wheel & Castor
for further support.
1. Check your remote LED lights up when button #1 is pressed
-
Repeat the pairing procedure

GTR064 Movement Issue

CAUTION
(Refer fig 1)
(Refer fig 2 – 4)
(Refer fig 5 & 6)
(Refer fig 7)
(Refer fig 8)
Fig 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GTR064 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Richmond GTR064

  • Page 1 5. Photocell settings or mounting is incorrect (Refer fig 8) Step-by-Step Troubleshooting *If you are uncomfortable or unsure about performing any of these tests please contact Richmond Wheel & Castor for further support. 1. Check your remote LED lights up when button #1 is pressed...
  • Page 2 2. The gates are factory set for a Right-Hand opening gate. Please check your settings as below For a Left-Hand opening gate, you will need to make three changes o Magnet positions are reversed (fig 2) o Dip Switch number 5 is set to ON (fig 3) o 2 out of the 3 wires in J10 wiring terminal need to be changed (fig 4)
  • Page 3 3. Check the limit switch magnets to make sure they are positioned correctly If the magnets are more than 10mm from the motor housing the limit switch may not activate correctly If the magnets are set too close to the end of the gate, the gate may hit the catch or stopper before the magnet is able to read its position correctly Fig 5 Fig 6...
  • Page 4 Dip switch #8 should be OFF if NOT using a photocell The J1 terminal on the PC board should also have a bridge wire between terminals 5 & 6 If your issue remains, please contact Richmond Wheel & Castor for further technical support...