Slim Duct Type - Fujitsu AU G18LVLB Series Design & Technical Manual

1 phase type simultaneous multi system
Hide thumbs Also See for AU G18LVLB Series:
Table of Contents

Advertisement

6-4-2.

SLIM DUCT TYPE

This table is created using the maximum capacity.
MODEL
: ARG18LL x 3
AFR
47.0
°CDB
-15
-10
-5
0
5
7
10
15
20
24
AFR: Airflow Rate (m³/min.)
TC: Total Capacity (kW)
IP: Input Power (kW)
°CDB
16
°CWB
TC
IP
-16
11.12
4.59
10.85
-11
12.58
4.59
12.28
-7
14.04
4.59
13.70
-2
15.49
4.59
15.12
3
16.95
4.59
16.55
6
17.54
4.59
17.12
8
17.59
4.59
17.17
10
17.67
3.94
17.25
15
17.75
3.90
17.33
18
17.82
3.49
17.39
- (02-48) -
Indoor temperature
18
20
TC
IP
TC
IP
4.68
10.59
4.78
4.68
11.98
4.78
4.68
13.37
4.78
4.68
14.76
4.78
4.68
16.14
4.78
4.68
16.70
4.78
4.68
16.75
4.78
4.02
16.83
4.10
3.98
16.91
4.06
3.57
16.97
3.64
22
24
TC
IP
TC
IP
10.33
4.88
10.06
4.97
11.68
4.88
11.38
4.97
13.03
4.88
12.70
4.97
14.39
4.88
14.02
4.97
15.74
4.88
15.34
4.97
16.28
4.88
15.87
4.97
16.33
4.88
15.91
4.97
16.41
4.18
15.99
4.24
16.48
4.14
16.06
4.20
16.55
3.71
16.12
3.77

Advertisement

Table of Contents
loading

Table of Contents