AIR CONDITIONER Cassette type DESIGN & TECHNICAL MANUAL SINGLE INDOOR AU G12LVLB AU G14LVLB AU G18LVLB AU G24LVLA OUTDOOR AO G12LALL AO G14LALL AO G18LALL AO G24LALA...
FEATURES MODEL AUG12LVLB / AOG12LALL AUG14LVLB / AOG14LALL AUG18LVLB / AOG18LALL AUG24LVLA / AOG24LALA FEATURES Energy efficiency class MODEL AU G12LVLB AU G14LVLB AU G18LVLB AU G24LVLA Cooling Heating 2-stage turbo fan Quiet quality ...
Page 5
10°C HEAT Operation *Only available with Wireless RC. The room temperature can be set to go no lower than 10°C, thus ensuring that the room does not get too cold when not occupied. Caution) • When the room temperature is higher than 10°C, “ 10°C HEAT”...
REMOTE CONTROLLER WIRELESS REMOTE CONTROLLER FEATURES 4 mode timer setup available (ON / OFF / PROGRAM / SLEEP) Easy operation. Easy to change signal code (max. 4 units) by button operation. Simple function setting ...
Page 7
FUNCTIONS MODE button Selects the operating mode (AUTO, COOL, DRY, FAN, HEAT). /Start / end R.C. signal code change. (Max 4 types) 10°C HEAT button SET TEMP. button ( ▲ / ▼ ) Sets the indoor temp./ Sets R.C. signal code. ECONOMY button SLEEP button Pressed to select sleep timer.
SPECIFICATIONS CASSETTE MODEL Type INVERTER HEATPUMP Indoor unit AUG12LVLB AUG14LVLB AUG18LVLB AUG24LVLA Model name Outdoor unit AOG12LALL AOG14LALL AOG18LALL AOG24LALA Power source 230V ~ 50Hz Available voltage range 198-264V ~ 50Hz 3.50 4.30 5.20 6.80 Rated Btu/h 11950 14650 17700 23200 Cooling 0.90 - 4.40...
DIMENSIONS MODEL : AUG12LVLB, AUG14LVLB, AUG18LVLB, AUG24LVLA Unit : mm • Cassette grille mounting state 530: Hanging bolt position op view Be sure to leave Service access service access for future service at the designated position. Min. 450 Drain port Drain port Control box...
Page 11
INSTALLATION PLACE Unit : mm Strong and durable ceiling or more 1000 1000 or more or more 1800 or more Obstruction Floor H (The maximum height from floor to ceiling) Unit: mm Model name AU G12LVLB AU G14LVLB AU ...
FAN PERFORMANCE 7-1. AIR VELOCITY DISTRIBUTION Note: Condition MODEL : AUG12LVLB Fan speed : High Operation mode : Fan 4-way air outlet Ceiling mode : Standard Unit : m/s 0.25 0.25 0.25 0.25 TOP VIEW VERTICAL LOUVER : Upward Unit : m/s 0.25...
Page 18
Note: Condition Fan speed : High Operation mode : Fan 3-way air outlet Ceiling mode : Standard Unit : m/s 0.25 0.25 0.25 TOP VIEW VERTICAL LOUVER : Upward Unit : m/s SIDE VIEW 0.25 VERTICAL LOUVER 0.25 : Upward Unit : m/s 0.25 0.25...
Page 19
Note: Condition MODEL : AUG14LVLB Fan speed : High Operation mode : Fan 4-way air outlet Ceiling mode : Standard Unit : m/s 0.25 0.25 0.25 0.25 TOP VIEW VERTICAL LOUVER : Upward Unit : m/s 0.25 0.25 SIDE VIEW VERTICAL LOUVER...
Page 20
Note: Condition Fan speed : High Operation mode : Fan 3-way air outlet Ceiling mode : Standard Unit : m/s 0.25 0.25 0.25 TOP VIEW VERTICAL LOUVER : Upward Unit : m/s SIDE VIEW 0.25 0.25 VERTICAL LOUVER : Upward Unit : m/s SIDE VIEW 0.25...
Page 21
Note: Condition MODEL : AUG18LVLB Fan speed : High Operation mode : Fan 4-way air outlet Ceiling mode : Standard Unit : m/s 0.25 0.25 0.25 0.25 TOP VIEW VERTICAL LOUVER : Upward Unit : m/s 0.25 0.25 SIDE VIEW VERTICAL LOUVER...
Page 22
Note: Condition Fan speed : High Operation mode : Fan 3-way air outlet Ceiling mode : Standard Unit : m/s 0.25 0.25 0.25 TOP VIEW VERTICAL LOUVER : Upward Unit : m/s SIDE VIEW 0.25 0.25 VERTICAL LOUVER : Upward Unit : m/s SIDE VIEW 0.25...
Page 23
Note: Condition MODEL : AUG24LVLA Fan speed : High Operation mode : FAN 4-way air outlet Ceiling mode : Standard Unit : m/s 0.25 0.25 0.25 0.25 TOP VIEW VERTICAL FLAP : Upward Unit : m/s 0.25 SIDE VIEW 0.25 VERTICAL FLAP...
Page 24
Note: Condition MODEL : AUG24LVLA Fan speed : High Operation mode : FAN 3-way air outlet Ceiling mode : Standard Unit : m/s 0.25 0.25 0.25 TOP VIEW VERTICAL FLAP : Upward Unit : m/s SIDE VIEW 0.25 0.25 VERTICAL FLAP...
7-2. AIRFLOW 7-2-1. STANDARD CEILING MODE MODEL : AUG12LVLB Cooling Number of Fan speed rotations Airflow (r.p.m) HIGH QUIET Heating Number of Fan speed rotations Airflow (r.p.m) HIGH QUIET - (01 - 22) -...
Page 26
MODEL : AUG14LVLB Cooling Number of Fan speed rotations Airflow (r.p.m) HIGH QUIET Heating Number of Fan speed rotations Airflow (r.p.m) HIGH QUIET - (01 - 23) -...
Page 27
MODEL : AUG18LVLB Cooling Number of Fan speed rotations Airflow (r.p.m) HIGH QUIET Heating Number of Fan speed rotations Airflow (r.p.m) HIGH QUIET - (01 - 24) -...
Page 28
MODEL : AUG24LVLA Cooling Number of Fan speed rotations Airflow (r.p.m.) HIGH QUIET zHeating Number of Fan speed rotations Airflow (r.p.m.) HIGH QUIET - (01 - 25) -...
Page 29
7-2-2. HIGH CEILING MODE MODEL : AUG12LVLB Cooling Number of Fan speed rotations Airflow (r.p.m) HIGH QUIET Heating Number of Fan speed rotations Airflow (r.p.m) HIGH QUIET - (01 - 26) -...
Page 30
MODEL : AUG14LVLB Cooling Number of Fan speed rotations Airflow (r.p.m) HIGH QUIET Heating Number of Fan speed rotations Airflow (r.p.m) HIGH QUIET - (01 - 27) -...
Page 31
MODEL : AUG18LVLB Cooling Number of Fan speed rotations Airflow (r.p.m) HIGH QUIET Heating Number of Fan speed rotations Airflow (r.p.m) HIGH QUIET - (01 - 28) -...
Page 32
MODEL : AUG24LVLA Cooling Number of Fan speed rotations Airflow (r.p.m.) 1030 HIGH 1050 QUIET zHeating Number of Fan speed rotations Airflow (r.p.m.) 1000 HIGH 1030 QUIET - (01 - 29) -...
ELECTRIC CHARACTERISTICS Model Name AUG12LVLB AUG14LVLB AUG18LVLB AUG24LVLA Voltage 230 ~ Power Supply Frequency Max Operating Current 0.24 0.28 0.38 0.30 Connection Cable *1) Wiring Spec. Limited wiring length *1) Wiring Spec. Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005) - (01 - 33) -...
SAFETY DEVICES Model Protection form AUG12LVLB AUG14LVLB AUG18LVLB AUG24LVLA Circuit protection Current fuse (PCB) 250V 3.15A Thermal protection 138 ± 15 °C OFF Fan motor protection program 105 ± 20 °C ON - (01 - 34) -...
EXTERNAL INPUT & OUTPUT Connector INPUT OUTPUT REMARKS CN102 Control input — See external CN103 — Operation status output input/output settings for details. — Fresh air control output 11-1. EXTERNAL INPUT CONTROL INPUT (Operation/Stop or Forced stop) The air conditioner can be remotely operated by means of the following on-site work. "Operation/Stop"...
11-2. EXTERNAL OUTPUT OPERATION STATUS OUTPUT An air conditioner operation status signal can be output. Circuit diagram example Indoor Connected unit control PC board Connector Ex.)Relay unit Ex.)Display 24V DC Relay power supply *10 m Signal Field supply * Make the distance from the PC board to the connected unit within 10m.
Page 40
FRESH AIR CONTROL OUTPUT A signal linked to air conditioner indoor fan ON can be output. * However, signal becomes OFF during cold air prevention control operation. Circuit diagram example Indoor Connected unit control PC board Ex.) Fan Ex.) Relay unit 12 V Connector...
FUNCTION SETTINGS 12-1. INDOOR UNIT INDOOR UNIT DIP SW Remote controller address setting Jumper Wire Setting forbidden SWITCH POSITION MAIN PCB Indoor unit Printed circuit board DIP-SW SETTING Remote controller address setting A number of indoor units can be operated at the same time using a wired remote controller. Set the unit number of each indoor unit using the DIP switches on the indoor unit circuit board.
12-2. INDOOR UNIT (Setting by remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit to malfunction. • After the power is turned on, perform the “FUNCTION SETTING” according to the installation conditions using the remote controller.
Page 43
CONTENTS OF FUNCTION SETTING • Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in accordance with the installed condition. After the power is turned on, perform the Function Setting on the remote control. •...
Page 44
4) Cooler room temperature correction Depending on the installed environment, the room temperature sensor may require a correction. The settings may be selected as shown in the table below. ( . . .Factory setting) Setting Description Function Number Setting Value Standard ...
Page 45
10) Indoor unit fan control for energy saving (Only cooling mode) Enable or disable indoor unit fan control when the outdoor unit is stopped. ( . . .Factory setting) Setting Description Function Number Setting Value *If setting value is “00”: When the outdoor unit is stopped, the indoor unit fan operates following the setting on the remote controller continuously.
Page 46
REMOTE CONTROLLER SIGNAL CODE SETTING Use the following steps to select the signal code of the remote controller. (Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code.) 1.
OPTIONAL PARTS 13-1. CONTROLLER Exterior Parts name Model No. Summary Large and full-dot liquid crystal Wired Remote screen, wide and large keys UTY-RVN M Controller easy to press, user-intuitive arrow key. Wired remote Unit control is performed by UTY-RNN M controller wired remote controller Simple remote...
13-3. OTHERS Exterior Parts name Model No. Summary Air outlet shutter plate is installed Air outlet UTR-YDZB at the air outlet when 3-way shutter plate direction is performed. Insulation Install when the under roof Insulation kit condition is expected to be UTZ-KXGC for high humidity the humidity of over 80 % and...
Page 49
2. OUTDOOR UNIT SINGLE TYPE : AOG12LALL AOG14LALL AOG18LALL AOG24LALA DTR_AO099E_02 2013.02.28...
SPECIFICATIONS Type INVERTER HEAT PUMP Model name AO G12LALL AO G14LALL AO G18LALL AO G24LALA Power source 230V ~ 50Hz Available voltage range 198 - 264V ~ 50Hz Starting current Cooling 1780 1910 2000 2470 Airflow rate Heating 1630 1740...
DIMENSIONS MODEL : AOG12LALL, AOG14LALL, AOG18LALL, AOG24LALA (Unit : mm) Top view Front view AO G12LALL AO G24LALA AO G14LALL AO G18LALL Air flow Side view Bottom view INSTALLATION PLACE When there are obstacles at When there are obstacles at When there are obstacles at the the back or front sides.
CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE This table is created using the maximum capacity. MODEL : AOG12LALL Pipe length (m) COOLING 0.903 0.894 0.867 Û 1 0.964 0.918 0.909 0.881 Indoor unit is higher than 0.988 0.968 0.922...
Page 57
This table is created using the maximum capacity. MODEL : AOG14LALL Pipe length (m) COOLING 0.953 0.950 0.947 Û 1 0.983 0.968 0.966 0.962 Indoor unit is higher than 0.988 0.987 0.972 0.970 0.966 outdoor unit. 0.992 0.992 0.991 0.976 0.974...
Page 58
This table is created using the maximum capacity. MODEL : AOG18LALL Pipe length (m) COOLING 0.953 0.950 0.947 Û 1 0.983 0.968 0.966 0.962 Indoor unit is higher than 0.988 0.987 0.972 0.970 0.966 outdoor unit. 0.992 0.992 0.991 0.976 0.974...
Page 59
This table is created using the maximum capacity. MODEL : AOG24LALA Pipe length (m) COOLING 0.963 0.961 0.959 Û 1 0.984 0.981 0.979 0.977 0.975 Indoor unit is higher than 0.988 0.988 0.985 0.983 0.981 0.979 outdoor unit. 0.992 0.992 0.992...
AIRFLOW MODEL : AOG12LALL Cooling Number of rotations Airflow (r.p.m.) 1780 1048 Heating Number of rotations Airflow (r.p.m.) 1630 MODEL : AOG14LALL Cooling Number of rotations Airflow (r.p.m.) 1910 1124 Heating Number of rotations Airflow (r.p.m.)
Page 62
MODEL : AOG18LALL Cooling Number of rotations Airflow (r.p.m.) 2000 1177 Heating Number of rotations Airflow (r.p.m.) 1910 1124 MODEL : AOG24LALA Cooling Number of rotations Airflow (r.p.m.) 2470 1050 1454 Heating Number of rotations Airflow...
ELECTRIC CHARACTERISTICS Model name AOG12LALL AOG14LALL AOG18LALL AOG24LALA Voltage 230 ~ Power supply Frequency *1) Max operating current 10.0 12.5 13.5 Starting Current Main Fuse (Circuit breaker) *2) Wiring Spec. Current Power Cable *1) The maximum current is the total current of indoor unit and outdoor unit. *2) Wiring Spec.: Selected Sample (Selected based on Japan Electrotechnical Standards and Codes Committee E0005)
SAFETY DEVICES Model Protection form AO G12LALL AO G14LALL AO G18LALL AO G24LALA 250V 20A Current fuse (Near the terminal) 250V 5A Circuit protection Current fuse 250V 15A (Main printed 250V 3.15A circuit board) Fan motor Thermal protection OFF : 100 °C...