10) Cold air prevention
This setting is to disable the cold air prevention function during heating operation. When
disabled, the fan setting will always follow the setting on the remote controller. (Excluding
defrost mode)
Function number
Setting value
43
11) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
Function number
Setting value
44
12) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function number
Setting value
46
13) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when
the outdoor unit is stopped during cooling operation.
Function number
Setting value
49
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently
at a very low speed.
14) Primary and secondary settings
Set the indoor unit that is connected to the outdoor unit using a transmission cable as the
primary.
Function number
Setting value
51
Setting description
00
Enable
01
Disable
Setting description
00
01
02
03
Setting description
00
Operation/Stop mode
01
(Setting prohibited)
02
Forced stop mode
Setting description
00
Disable
01
Enable
Setting description
00
Primary
01
Secondary
- (04-71) -
Factory setting
Factory setting
A
B
C
D
Factory setting
Factory setting
Factory setting