6) Room temperature sensor control for cooling
Depending on the installed environment, correction of the room temperature sensor may be
required.
Select the appropriate control setting according to the installed environment.
Function number
Setting value
30
In case of Slim duct type and Floor/Ceiling type models: In floor console installations, select
"01".
7) Room temperature sensor control for heating
Depending on the installed environment, correction of the room temperature sensor may be
required.
Select the appropriate control setting according to the installed environment.
Function number
Setting value
31
In case of Slim duct type and Floor/Ceiling type models: In floor console installations, select
"01".
8) Auto restart
Enable or disable automatic restart after a power interruption.
Function number
Setting value
40
* Auto restart is an emergency function such as for power outage etc.
Do not attempt to use this function in normal operation.
Be sure to operate the unit by remote controller or external device.
9) Room temperature sensor switching
(Only for Wired remote controller)
When using the Wired remote controller temperature sensor, change the setting to "Both" (01).
Function number
Setting value
42
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
* Remote controller sensor must be turned on by using the remote controller.
Setting description
00
Standard
01
Slightly lower control
02
Lower control
03
Higher control
Setting description
00
Standard
01
Lower control
02
Slightly higher control
03
Higher control
Setting description
00
Enable
01
Disable
Setting description
00
Indoor unit
01
- (04-70) -
Factory setting
Factory setting
Factory setting
Factory setting
Both