Function Details - Fujitsu AU G18LVLB Series Design & Technical Manual

1 phase type simultaneous multi system
Hide thumbs Also See for AU G18LVLB Series:
Table of Contents

Advertisement

6-6.

FUNCTION DETAILS

Function no.
1)
02
Refrigerant circuit address
2)
11
Filter sign
3)
20
Ceiling height
21
4)
Static pressure
26
5)
22
Outlet directions
6)
30
Room temperature sensor control for cooling
7)
31
Room temperature sensor control for heating
8)
40
Auto restart
9)
42
Room temperature sensor switching
10)
43
Cold air prevention
11)
44
Remote controller custom code
12)
46
External input control
13)
49
Indoor unit fan control for energy saving for cooling
14)
51
Primary and secondary settings
1) Refrigerant circuit address
Assign the same number to all of the indoor units connected to an outdoor unit.
Function Number
02
2) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the
estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number
11
Intervals will differ depending on the indoor unit type as follows:
Setting description
Standard
Long interval
Short interval
Functions
Setting Value
Refrigerant circuit address
00 to 15
Setting value
Setting description
00
01
02
03
Simultaneous Multi System
Compact
Slim duct
cassette
2500 hours
400 hours
4400 hours
1000 hours
1250 hours
200 hours
- (04-68) -
Simultaneous Multi System
Compact
Slim duct
Duct
cassette
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
00
01
14
15
Factory setting
Standard
Long interval
Short interval
No indication
Floor/
Duct
ceiling
2500 hours
400 hours
4400 hours
1000 hours
1250 hours
200 hours
Floor/
ceiling
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z