Fujitsu AU G18LVLB Series Design & Technical Manual page 231

1 phase type simultaneous multi system
Hide thumbs Also See for AU G18LVLB Series:
Table of Contents

Advertisement

INSTALLATION
Mounting of indoor unit
z
Please refer to the installation manual provided with the indoor unit for mounting.
Please refer to the diagram below for installation height.
When installing this product to existing indoor units, please adjust the installation height of the
indoor units to height 230-235mm.
Indoor unit
Fresh air intake kit
Installation of the fresh air intake kit
z
Installing the Fresh Air Intake Kit with the wrong direction is a cause of water leakage.
Provisionally attach the "DRAIN", "PIPE" of the Fresh Air Intake Kit to the indoor unit foam-
sealed "DRAIN", "PIPE", following the direction of the indoor unit, using the metal fittings of the
combined diagram.
Metal fittings x 2
(Unit : mm)
Metal hanging fastener
Ceiling
CAUTION
"DRAIN"
 
- (04-89) -
"PIPE"
"DRAIN"
"PIPE"
Bolt x 4