Conformance To Vds2463 - AddSecure IRIS-4 Technical Reference Manual

Table of Contents

Advertisement

8.6

Conformance to VdS2463

For conformance to the VdS2463 standard, the following must apply:
1.
Installation should conform to the instructions set out above.
2.
Access to all configuration parameters on the terminal, including the addresses of the Alarm Receiving
Equipment (ARE) is restricted by use of an installer password. A default installers password (111111) is set
as a factory default. This must be changed to another 6-digit number, preferably during installation, or
later.
3.
Shielded cables should not be used for interconnection with the IAS-CIE.
4.
Faults on the inputs to the terminal that act as interfaces to the alarm system will be reported to the alarm
receiving equipment as SIA code NT9107, and a restore as SIA code NR9107. Note these codes can be
modified on the alarm receiving equipment if so required.
5.
If the terminal shares IP transmission facilities with other systems, this should be arranged so that routing
of messages to and from the terminal is given priority higher than other messages.
6.
The status of the terminal inputs that act as interfaces to the alarm system is sent to the ARE whenever the
terminal is started or restarted. These are indicated as either "activated" or "not activated" and can be
viewed by the operator of the ARE as required.
7.
The serial communication lines must not be the primary signaling method. They may, however, be used for
additional information.
Remote activation of relays via the ISA receiver at the ARC is prohibited when in VdS mode.
.
IRIS-4 Technical Reference Manual.docx 12/01/2023
page 53