9.3 Outdoor Unit - BMS500-AAM036-1CSXHC,
BMS500-AAM048-1CSXRC, BMS500-AAM048-1CSXHC
9.3.1 Removing the fan assembly
1. Stop operation of the system and turn "OFF" the power at the disconnect.
2. Remove the air outlet grille (8 screws).
Figure 135
3. Remove the nut fixing the fan, and remove the fan.
Figure 136
4. Remove the top cover (4 screws).
Bosch Climate 5000 Series Ductless Air Conditioner / Heat Pump Multi Zone Outdoor Units (01.2023)
Screws of top cover
Figure 137
5. Remove the front side panel (1 screw).
Figure 138
6. Disconnect the fan motor connectors FAN1 (3p, white) and FAN2 (3p, white)
from DC motor driver board.
Figure 139
Service Manual
| 97