Siemens sinamics g120 Hardware Installation Manual page 64

Hide thumbs Also See for sinamics g120:
Table of Contents

Advertisement

Technical specifications
6.2 Specific technical data
Table 6- 5
PM230, IP20, Frame Sizes B, 3 AC 380 V ... 480 V
Order No. - without filter
Order No. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL
Power loss
Required cooling air flow
Cross section of line and motor cables
Tightening torque for line and motor cables
Weight without filter
Weight with filter
Table 6- 6
PM230, PT, Frame Sizes B, 3 AC 380 V ... 480 V
Order No. - without filter
Order No. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL
Power loss
Required cooling air flow
Cross section of line and motor cables
Tightening torque for line and motor cables
Weight without filter
Weight with filter
64
6SL3210...
...1NE21-0UL1
6SL3210...
...1NE21-0AL1
4 kW
10.5 A
10.2 A
3 kW
8.0 A
7.7 A
3NE1 813-0
AJT15 / 3NE1 813-0
0.12 kW
9.2 l/s
1.5 ... 6 mm
16 ... 10 AWG
0.6 Nm / 5 lbf in
2.8 kg
3 kg
6SL3211...
...1NE21-8UL1
6SL3211...
...1NE21-8AL1
7.5 kW
18.6 A
18 A
5.5 kW
13.6 A
13.2 A
3NE1 815-0
AJT25 / 3NE1 815-0
0.22 kW
9.2 l/s
1.5 ... 6 mm
16 ... 10 AWG
0.6 Nm / 5 lbf in
3.4 kg
3.6 kg
...1NE21-3UL1
...1NE21-3AL1
5.5 kW
13.6 A
13.2 A
4 kW
10.5 A
10.2 A
3NE1 814-0
AJT20 / 3NE1 814-0
0.15 kW
9.2 l/s
1.5 ... 6 mm
2
2
16 ... 10 AWG
0.6 Nm / 5 lbf in
2.8 kg
3 kg
2
Power Module PM230, IP20 / Push-through technology (PT)
Hardware Installation Manual, 06/2014, A5E34331322B AA
...1NE21-8UL1
...1NE21-8AL1
7.5 kW
18.6 A
18 A
5.5 kW
13.6 A
13.2 A
3NE1 815-0
AJT25 / 3NE1 815-0
0.22 kW
9.2 l/s
1.5 ... 6 mm
2
16 ... 10 AWG
0.6 Nm / 5 lbf in
2.8 kg
3 kg

Advertisement

Table of Contents
loading

Table of Contents