Handling Precautions - Mitsubishi Electric FREQROL HC Instruction Manual

Transistorized inverter
Table of Contents

Advertisement

1.1.3 Handling precautions

The following system is required to operate the inverter. Install the high power factor converter in a proper
position. For the selection and specifications of each peripheral device, refer to "Precautions for Selecting
Peripheral Devices" on page 52:
Ground
Name
Use the power supply within the
Power supply
permissible power supply specifications
of the high power factor converter.
Earth leakage
The breaker should be selected with
circuit
care since a large inrush current flows
breaker or no-fuse
in the high power factor converter at
breaker
power on.
Install the magnetic contactor to
ensure safety.
Magnetic
When installed, do not use it to start
contactor
or stop the inverter. It might reduce
the high power factor converter life.
Make sure that the reactor has a
Reactor 1
proper capacity which matches the
FR-HCL01
high power factor converter capacity.
Make sure that the external box has a
External box
proper capacity which matches the
FR-HCB
high power factor converter capacity.
Make sure that the reactor has a
Reactor 2
proper capacity which matches the
FR-HCL02
high power factor converter capacity.
Install
correctly.
High power factor
Note: Do not install a no-fuse breaker
converter
(NFB) across terminals P-P and
N-N of the high power factor
converter and the inverter.
Make
sure
compatible with the FR-HC.
Inverter
Connect the inverter suitable for the
capacity of the high power factor
converter.
Do not connect a power capacitor,
surge suppressor or radio noise filter
to the output side.
Devices
Note: When
connected to the
breaker (NFB) on the output
output
side,
manufacturer for selection of
no-fuse breaker.
Connect the motor suitable for the
Motor
capacity.
To prevent an accidental electric shock,
always ground the high power factor
Ground
converter, external box, inverter and
motor.
- 6 -
Description
and
wire
the
equipment
that
the
inverter
is
installing
a
no-fuse
contact
the
NFB
Refer to Page:
56
55
55
62
64
62
13
56
Instruction
manuals of the
devices
connected on
the output side
Inverter
instruction
manual
Inverter
instruction
manual