Data sheet
HCV 460
164
Specification
Max. flow at 100Pa
Max. rated flow at 100Pa
Operating range DIBt
Working range Passivhaus at 100Pa
EN 13141-7 reference flow @50Pa
Performance
Temperature efficiency in accordance
with EN13141-7l
Filters in accordance with EN779: 2012
Filters in accordance with ISO 16890
Ambient temperature for installation
Outdoor temperature range without
installed preheater
Outdoor temperature with pre-heater
installed
Maximum absolute humidity
of extract air
Cabinet:
Dimensions (without brackets)
Spigots/duct connections
Weight
Thermal conductivity -
polystyrene insulation
Heat transfer coefficient -
polystyrene insulation
Fire class - polystyrene insulation
Leakage (outside and inside) in
accordance with EN 13141-7
Drainage hose
Cabinet colour
Electrical
Voltage
Max. power consumption
(without/with preheater)
Frequency
IP class
* The use of the preheating coil is recommended at outdoor temperatures below -3°C to
ensure balanced operation
** +20mm fitting
INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Abbr .
Unit
V
m3/h
100Pa
V
m3/h
max nom.
V
m3/h
DIBt
V
m3/h
PHI
V
m3/h
REF
h
SUP
class
class
t
SURR
t
ODA
t
ODA
x
g/kg
W x H x D
mm
Ø
mm
m
l
W/(mK)
U
W/(m
-
Ø/length
" / m
RAL
U
P
f
class
Appendix: Technical data
HCV 460 P2
460
360
70 - 360
106 - 270
252
%
86
-
G4/G4 (F7 optional)
ISO Coarse (epM1 > 50%
-
optional)
°C
from +12 to +40
°C
from -12 to +50
°C
from -25 to +50
10
540 x 1050x549 **
Ø160 - female
kg
40
0.031
K)
U<1
2
DIN 4102 Class B2
-
EN 13501 Class E
< 2 % (Class A1)
3/4" - 2 m
-
9016
V
230
W
230/2080
Hz
50
-
21