Dantherm HCV 300 Manual page 161

Hide thumbs Also See for HCV 300:
Table of Contents

Advertisement

Available languages

Available languages

INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Maintenance and care: Error list
A B
16 R
Error
C
Error
code
2
E16
Firmware 2.9 and
up:
FPC fault (option)
Only active if the
"Fire Protection
Controller" acces-
sory is connected
to the unit.
No communica-
tion with the
fire protection
controller
There is no posi-
tion feedback for
fire dampers
Error in monthly,
weekly or manual
test of fire damp-
ers
Action
Possible cause
required
Fire protection
Check connection
controller with
to fire protection
this address has
controller
previously been
installed but can
no longer be
reached
A fire damper
Check power supply
is closed, but
to fire dampers
should be open
Check fire dampers
internal fire detector
Fire damper stuck
The fire damper is
in either open or
blocked.
closed position
Fire dampers are con-
nected incorrectly
Fire damper defec-
tive
Reset
Perform a
manual reset
by pressing the
alarm button on
the membrane
panel or by
turning the unit
off/on
161