Technical Data
16
FRCC.PC.041.A1.02
Electronic driver
Model
Type
Supported devices
Communication port
Communication capabilities
Compressor speed selection
Battery protection level selection
Protections
Programmable running modes
Setup by default
Nominal performance at
Cooling capacity
Cooling capacity
Input power
EER
COP
Current
Test Conditions
Evaporating temperature
Condensing temperature
Liquid temp. entering expansion
Ambient and return temp.
Voltage
*Only for voltage supply
FDC3
Fully digital & programmable μP based
12V/0.5A Fan
Compressor speed or battery protection level switcher
Alarm LED
15V/25mA electronic thermostat
5V/25mA Electronic Integral Manager
Serial Port Interface (SPI)
RS-232 serial port
2-digit, 4-level switcher
Alarm LED
By programming or switching*
By Programming or switching*
*only one at a time
Battery protection
Fan over current
Starting failure
Compressor overload
Electronic driver overheat
Fan over current
Starting failure
Compressor overload
Electronic driver overheat
Standard
Smart Speed
Sleep
Sleep Energy Saving
Slave
Running mode: Standard
Speed selection: external switcher
Lower/higher speed: 2000/3500 r.p.m.
Battery protection: fixed voltage level; standard system
Cut-out (12/24/42 V systems): 12/22/38,5 V
Cut- in (12/24/42 V systems): 10.8/20.0/36.2 V
3 minutes thermostat delay: on
rpm
2000
2500*
W
577
kCal/h
497
W
247
kCal/(Wh)
2.01
W/W
2.34
A
10.3
ºC
ºC
ºC
ºC
V DC
V DC
3000*
3500*
712
842
968
613
725
834
315
388
468
1,95
1.87
1.78
2,26
2,17
2,07
13.1
16.2
19.5
+7,2
55
32
35
24
24-42